Fisher FIELDVUEDVC6200f Instruction Manual page 251

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table E‐9. Control Selector Function Block System Parameters Definitions
Label
PARAMETER_NAME
Output Scale
OUT_SCALE
EU_100
EU_0
UNITS_INDEX
DECIMAL
Grant Deny
GRANT_DENY
GRANT
DENY
Status Options
STATUS_OPTS
SEL_1
STATUS
VALUE
SEL_2
STATUS
VALUE
SEL_3
STATUS
VALUE
SEL_TYPE
BKCAL_IN
STATUS
VALUE
OUT_HI_LIM
OUT_LO_LIM
Index
RO /
Block
Number
RW
Mode
8
RW
OOS
8.1
RW
OOS
8.2
RW
OOS
8.3
RW
OOS
8.4
RW
OOS
9
Bit 0: Program
Bit 1: Tune
Bit 2: Alarm
Bit 3: Local
9.1
RW
ALL
Bit 4: Operate
Bit 5: Service
Bit 6: Diagnostic
Bit 0: Program Denied
Bit 1: Tune Denied
Bit 2: Alarm Denied
Bit 3: Local Denied
9.2
RW
ALL
Bit 4: Operate Denied
Bit 5: Service Denied
Bit 6: Diagnostic Denied
0: IFS (Initiate Fault State)
if BAD IN
10
RW
OOS
2: Use Uncertain as Good
11
RW
ALL
11.1
RW
ALL
11.2
RW
ALL
12
RW
ALL
12.1
RW
ALL
12.2
RW
ALL
13
RW
ALL
13.1
RW
ALL
13.2
RW
ALL
0: Uninitialized
MAN
1: High
14
RW
OOS
2: Low
3: Middle
15
RW
ALL
15.1
RW
ALL
15.2
RW
ALL
16
RW
ALL
OUT_SCALE +/- 10%
17
RW
ALL
OUT_SCALE +/- 10%
Range
Initial Value
100
0
%
0
All bits: 0
All bits: 0
All bits: 0
Bad
Not Connected
Not Limited
Bad
Not Connected
Not Limited
Bad
Not Connected
Not Limited
0
Bad
Not Connected
Not Limited
100
0
DVC6200f Digital Valve Controller
CSEL Function Block
Description
Data Type: DS‐68
The high and low scale values, engineering units
code, and number of digits to the right of the
decimal point associated with OUT.
Data Type: DS‐70
Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block. Not used by the
device.
Data Type: Bit String, 2 bytes
0=disable
1=enable
Allows you to select options for status handling
and processing.
Data Type: DS‐65
The first input value to the selector.
Data Type: DS‐65
The second input value to the selector.
Data Type: DS‐65
The third input value to the selector.
Data Type: UINT8
The selector type: High, Low, or Middle value.
If selector type is not selected the block will not
transition from OOS.
Data Type: DS‐65
The analog input value and status from another
block's BKCAL_OUT output that is used by an
upstream block for bumpless transfer.
Data Type: Float
The maximum output value allowed.
Data Type: Float
The minimum output value allowed.
February 2017
251

Advertisement

Table of Contents
loading

Table of Contents