Fisher FIELDVUEDVC6200f Instruction Manual page 95

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Output Blk Timeout
OUTPUT_BLK_TIMEOUT
Drive Current Alert Point
DRIVE_CURRENT_ALRT_PT
Drive Current Alert Time
DRIVE_CURRENT_TIME
Temperature Hi Alert Point
TEMP_HI_ALRT_PT
Temperature Lo Alert Point
TEMP_LO_ALRT_PT
Supply Pressure Hi Alert Point
SUP_PRES_HI_ALRT_PT
Supply Pressure Lo Alert Point
SUP_PRES_LO_ALRT_PT
INST_ALERTS_CONFIG2
Travel Deviation Deadband
TVL_DEV_DB
Travel Accumulator Alert Point
TVL_ACCUM_ALRT_PT
Travel Accumulator Deadband
TVL_ACCUM_DB
Cycle Count Alert Point
CYCLE_COUNT_ALRT_PT
Cycle Count Deadband
CYCLE_COUNT_DB
Travel Open Deadband
TVL_OPEN_DB
Travel Closed Deadband
TVL_CLOSED_DB
Travel Lo Lo Alert Point
TVL_LO_LO_ALRT_PT
Travel Lo Lo Deadband
TVL_LO_LO_DB
Travel Lo Alert Point
TVL_LO_ALRT_PT
Travel Lo Deadband
TVL_LO_DB
Index
RO /
Mode
Number
RW
AUTO
Time >= 0, <= 800
MAN
83.3
RW
seconds
OOS
AUTO
83.4
RW
MAN
>=5% <= 100%
OOS
AUTO
MAN
83.5
RW
>= 0.25, <=120 seconds
OOS
AUTO
83.6
RW
MAN
> -76 F < 257 F
OOS
AUTO
83.7
RW
MAN
> -76 F < 257 F
OOS
AUTO
83.8
RW
MAN
>0, <=150
OOS
AUTO
83.9
RW
MAN
=>=0, <=150
OOS
84
AUTO
84.1
RW
MAN
>= 0, <= 100
OOS
AUTO
84.2
RW
MAN
>=0
OOS
AUTO
84.3
RW
MAN
0 to 100
OOS
AUTO
84.4
RW
MAN
>=0
OOS
AUTO
MAN
84.5
RW
0 to 100
OOS
AUTO
84.6
RW
MAN
>=0, <=100
OOS
AUTO
84.7
RW
MAN
>=0, <=100
OOS
AUTO
MAN
84.8
RW
-25 to 125
OOS
AUTO
MAN
84.9
RW
>=0, <=100
OOS
AUTO
84.10
RW
MAN
-25 to 125
OOS
AUTO
84.11
RW
MAN
>=0, <=100
OOS
Range
Initial Value
600
10
2
85.555 degC
(186 degF)
-52.77 degC
(-63 degF)
999.7 kPa
(145 psig)
103.4 kPa (15
psig)
2
1,000,000
1
1,000,000
1
1
1
-25
5
-25
5
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
Data Type: Float
The maximum time between
SETUP
updates from the AO or DO block to
the transducer block setpoint.
Data Type: Float
SETUP
(percent different) drive signal not
reaching I/P accurately.
Data Type: Float
(percent different) drive signal not
SETUP
reaching I/P accurately.
Data Type: Float
SETUP
Temperature HI Limits
Data Type: Float
SETUP
Temperature LO Limits
Data Type: Float
SETUP
Maximum supply pressure
Data Type: Float
SETUP
Minimum supply pressure
SETUP
Data Type: Float
Data Type: UINT32
SETUP
Alerts when accumulated travel is
too much
Data Type: Float
SETUP
Deadband
Data Type: UINT32
SETUP
Alerts when number of cycles is too
large.
Data Type: Float
SETUP
Deadband
Data Type: Float
SETUP
Deadband
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 26
& 30 regardless of alert enable state.
Data Type: Float
SETUP
Deadband
Data Type: Float
Alert when valve position is less than
SETUP
alert point. Controls DI channels 27
& 31 regardless of alert enable state.
Data Type:
SETUP
Deadband
February 2017
95

Advertisement

Table of Contents
loading

Table of Contents