DVC6200f Digital Valve Controller
ISEL Function Block
February 2017
Table E‐13. Input Selector Function Block Parameter Definitions
Label
PARAMETER_NAME
Input 1
IN_1
Input 2
IN_2
Input 3
IN_3
Input 4
IN_4
Disable Analog Input 1
DISABLE_1
Disable Analog Input 2
DISABLE_2
Disable Analog Input 3
DISABLE_3
Disable Analog Input 4
DISABLE_4
Select Type
SELECT_TYPE
Min Good
MIN_GOOD
Selected
SELECTED
Operator Select
OP_SELECT
264
Index
Block
RO / RW
Number
Mode
11
ALL
12
ALL
13
ALL
14
ALL
15
ALL
16
ALL
17
ALL
18
ALL
19
ALL
20
ALL
21
RO
N/A
22
ALL
Range
Initial Value
BAD
Status
Not Connected
constant
Value
0
BAD
Status
Not Connected
constant
Value
0
BAD
Status
Not Connected
constant
Value
0
BAD
Not Connected
Status
constant
Value
0
BAD
Status
Not Connected
constant
Value
0=Use
0 = Use
1=Disable
BAD
Not Connected
Status
constant
Value
0=Use
0 = Use
1=Disable
BAD
Status
Not Connected
constant
Value
0=Use
0 = Use
1=Disable
BAD
Status
Not Connected
constant
Value
0=Use
0 = Use
1=Disable
1=First Good
2=Minimum
3=Maximum
All Off
4=Middle
5=Average
6=Hot Spare
1 - 4
0
0 initial value only
Status
Value
Dynamic
0 - 8
BAD
Status
Not Connected
constant
Value
0
0 - 8
Instruction Manual
Description
Data Type: DS‐65
The block input value and status.
Data Type: DS‐65
The block input value and status.
Data Type: DS‐65
The block input value and status.
Data Type: DS‐65
The block input value and status.
Data Type: DS‐66
Enable/Disable for Input_1, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.
Data Type: DS‐66
Enable/Disable for Input_2, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.
Data Type: DS‐66
Enable/Disable for Input_3, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.
Data Type: DS‐66
Enable/Disable for Input_4, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.
Data Type: Unsigned8
Determines the selector action
Data Type: Unsigned8
The minimum number of inputs which are "good"
is less than the value of MIN_GOOD then set the
OUT status to "bad".
Data Type: DS‐66
The integer indicating the selected input number.
Data Type: DS‐66
An operator settable parameter to force a given
input to be used.
D103412X012