Resoure Block Parameter List - Fisher FIELDVUEDVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Resource Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shared Index Number indicates sub‐parameter.
Table 4‐3. Resource Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET_MODE
ACTUAL_MODE
PERMITTED_MODE
NORMAL_MODE
Block Error
BLOCK_ERR
Device State
RS_STATE
Index
RO /
Mode
Number
RW
1
RO
NA
0 to 65535
2
RW
NA
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
3: Auto
5.1
RW
ALL
7: OOS
3: Auto
6: IMAN (only during
5.2
RO
NA
initialization
7: OOS
3: Auto
5.3
RW
ALL
7: OOS
3: Auto
5.4
RW
ALL
7: OOS
0: Other
1: Configuration Error
3: Simulate Active
5: Device Fault State
Set
6: Need Maintenance
Soon
6
RO
N/A
9: Memory Failure
10: Lost Static Data
11: Lost NV Data
13: Need
Maintenance Now
14: Power‐up
15: OOS
0: Undefined
1: Start/Restart
2: Initialization
7
RO
N/A
3: On‐line Linking
4: On‐line
5: Standby
6: Failure
DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
Initial
Range
Value
Data Type: Unsigned16
The revision level of the static data. Increments
by one each time a static parameter changes.
0
The value is reset to 0 whenever a Restart with
Defaults is performed. See Restarting the
Instrument.
Data Type: Octet String
The user description of the intended application
Spaces
of the block. Null characters are not allowed in
this data type.
Data Type: Unsigned16
0
Used to identify groupings of blocks. The data is
not checked or processed by the block.
Data Type: Unsigned8
The identification number of the plant unit.
Devices in a loop or plant section can be
0
assigned with a common alert key to aid the
operator in determining location of alerts.
7: OOS
Data Type: DS‐69
The actual, target, permitted, and normal
N/A
modes.
3: Auto
7: OOS
3: Auto
Data Type: Bit String
0 = Inactive
1 = Active
Dynamic
Error status associated with hardware or
software for the resource block. When an error is
shown it may be broadcast to the host through
BLOCK_ALM.
Data Type: Unsigned8
5: Standby
State of the function block application state
machine.
February 2017
Description
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
33

Advertisement

Table of Contents
loading

Table of Contents