Table E‐13. Input Selector Function Block Parameter Definitions
Label
PARAMETER_NAME
Update Event
UPDATE_EVT
UNACKNOWLEDGED
UPDATE_STATE
TIME_STAMP
STATIC_REVISION
RELATIVE_INDEX
Block Alarm
BLOCK_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
In 5
IN_5
In 6
IN_6
In 7
IN_7
In 8
IN_8
Disable Analog Input 5
DISABLE_5
Disable Analog Input 6
DISABLE_6
Index
Block
RO / RW
Number
Mode
23
23.1
RW
N/A
23.2
RO
N/A
23.3
RO
N/A
23.4
RO
N/A
23.5
RO
N/A
24
24.1
RW
N/A
24.2
RO
N/A
24.3
RO
N/A
24.4
RO
N/A
24.5
RO
N/A
25
ALL
26
ALL
27
ALL
28
ALL
29
ALL
30
ALL
Range
Initial Value
0=Undefined
1=Acknowledged
0
2=Unacknowledged
0=Undefined
1=Update Reported
0
2=Updated not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
Extended Parameters
BAD
Status
Not Connected
constant
Value
0
BAD
Status
Not Connected
constant
Value
0
BAD
Status
Not Connected
constant
Value
BAD
Not Connected
Status
constant
Value
0
BAD
Status
Not Connected
constant
Value
0=Use
0 = Use
1=Disable
BAD
Not Connected
Status
constant
0
Value
0=Use
0 = Use
1=Disable
DVC6200f Digital Valve Controller
ISEL Function Block
Description
Data Type: DS‐73
This alert is generated by any change to the static
data.
Data Type: DS‐72
The block alarm is used for all configuration,
hardware, connection failure, or system problems
in the block. The cause of the alert is entered in the
subcode field. The first alert to become active will
set the active status in BLOCK_ERR. As soon as the
Unreported status is cleared by the alert reporting
task, another block alert may be reported without
clearing the Active status, if the subcode has
changed.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐65
Input value and status.
Data Type: DS‐66
Enable/Disable for Input_5, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.
Data Type: DS‐66
Enable/Disable for Input_6, If parameter is TRUE
then input is disabled. If parameter status is BAD it
is not evaluated.