ISEL Function Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentations and shared Index Numbers indicate sub‐parameters
Table E‐13. Input Selector Function Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Output
OUT
Output Range
OUT_RANGE
Grant Deny
GRANT_DENY
GRANT
DENY
Status Options
STATUS_OPTS
Index
Block
RO / RW
Number
Mode
1
RO
N/A
2
RW
ALL
3
RW
ALL
4
RW
ALL
5
5.1
RW
ALL
5.2
RO
ALL
5.3
RW
ALL
5.4
RW
ALL
6
RO
N/A
MAN
7
OOS
8
ALL
9
9.1
ALL
9.2
ALL
10
OOS
Range
Initial Value
0 to 65535
0
7 bit ASCII
spaces
0 to 65535
0
1 to 255
0
OOS until block
is configured,
OOS, MAN, AUTO
then last valid
target
OOS+MAN+
OOS+MAN+AUTO
AUTO
AUTO
1: Block
Configuration Error
Dynamic
14: Power Up
15: Out‐of‐Service
Status
OUT_RANGE
Dynamic
Value
EU at 100%
100
EU at 0%
0
Units Index
%
Decimal Point
0
0: Program
All bits: 0
1: Tune
2: Alarm
All bits:0
3: Local
2: Use Uncertain as
GOOD
All bits: 0
8: Uncertain if MAN
DVC6200f Digital Valve Controller
ISEL Function Block
Description
Data Type: Unsigned16
The revision level of the static data associated with
the function block. The revision value will be
incremented each time a static parameter value in
the block is changed.
Data Type: Octet String
The user description of the intended application of
the block.
Data Type: Unsigned16
The strategy field can be used to identify grouping
of blocks. This data is not checked or processed by
the block.
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting
alarms, etc.
Data Type: DS‐69
Valid Bits: 7: OOS, 4: MAN,
3: AUTO
The actual, target, permitted, and normal modes
of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String
0=Inactive
1=Active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown.
Data Type: DS‐65
The block output value and status.
Data Type: DS‐67
High and low scale values, engineering units code,
and number of digits to the right of the decimal
point associated with OUT.
Data Type: DS‐70
Options for controlling access of host computers
and local control panels to operating, tuning, and
alarm parameters of the block. Not used by device.
GRANT: 0=N/A, 1=granted
DENY: 0=N/A, 1=denied
Data Type: Bit String
Allows you to select options for status handling
and processing. The supported status option for
the input selector block is: "Use Uncertain as
Good", "Uncertain if Man mode."
February 2017
263