Fisher FIELDVUEDVC6200f Instruction Manual page 250

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
CSEL Function Block
February 2017
Control Selector Function Block Parameters
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shared Index Number indicates sub‐parameter
Table E‐9. Control Selector Function Block System Parameters Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Output
OUT
STATUS
VALUE
250
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
2
RW
ALL
3
RW
ALL
4
RW
ALL
1 to 255
5
Bit 3: Auto
5.1
RW
ALL
Bit 4: Man
Bit 7: OOS
Bit 3: Auto
Bit 4: Man
5.2
RO
N/A
Bit 6: Iman
Bit 7: OOS
Bit 3: Auto
Bit 4: Man
5.3
RW
ALL
Bit 7: OOS
Bit 3: Auto
5.4
RW
ALL
Bit 4: Man
Bit 7: OOS
Defined Bits
1: Configuration Error
6
RO
N/A
7: Input Failure
15: OOS
MAN
7
RW
OOS
MAN
7.1
RW
OOS
MAN
7.2
RW
OUT_SCALE +/- 10%
OOS
Range
Initial Value
0
Spaces
0
0
OOS
AUTO+MAN+
OOS
AUTO
Bad
Non Specific
Not Limited
Instruction Manual
D103412X012
Description
Data Type: Uint16
The revision level of the static data associated
with the function block. The revision value will be
incremented each time a static parameter value
in the block is changed.
Data Type: Octet String, 32 bytes
The user description of the intended application
of the block.
Data Type: Uint16
The strategy field can be used to identify
grouping of blocks. This data is not checked or
processed by the block.
Data Type: Uint8
A user-assigned identification number reported
in alarm messages from the block that allows HMI
applications to sort and filter alarms and events.
Set this parameter for each function block to
indicate the physical unit the function block is
associated with. This information can be used in
the host for sorting alarms, and so on.
Data Type: DS‐69
The actual, target, permitted, and normal modes
of the block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String, 2 bytes
0 = inactive
1 = active
This parameter reflects the error status
associated with the hardware or software
components associated with a block. It is a bit
string so that multiple errors may be shown.
Data Type: DS‐65
The block output value and status.