Fisher FIELDVUEDVC6200f Instruction Manual page 93

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Shutdown Alerts
SHUTDOWN_ALERTS_ACTIVE
INST_ALERTS_ENABLE
GROUP_1_ENABLE
Index
RO /
Mode
Number
RW
Same as
SHUTDOWN_TRIGGER
81.11
RO
[83.1-]
82
Bit 0: Check Alert
Bit 1: Drive Current
Bit 2: Drive Signal
Bit 3: Program Memory
Bit 4: Static Memory
Bit 5: I/O Processor
Bit 7: Output Block
Timeout
Bit 8: Blocks to Defaults
Bit 11: Travel Sensor
Bit 12: Port A Pressure
Sensor
Bit 13: Port B Pressure
Sensor
AUTO
Bit 14: Supply Pressure
MAN
82.1
Sensor
OOS
Bit 15: Temperature
Sensor
Bit 18: Pressure Fallback
Bit 19: Travel Deviation
Bit 21: Supply Pressure
High
Bit 22: Supply Pressure
Low
Bit 23: Temperature High
Bit 24: Temperature Low
Bit 27: Performance
Critical
Bit 28: Performance
Reduced
Bit 29: Performance Info
Range
Initial Value
All Bits: 0
·Drive Current
·Drive Signal
·Program Memory
·Static Memory
·I/O Processor
·Blocks Set to
Defaults
·Travel Sensor
·Pressure A Sensor
·Pressure B Sensor
·Supply Pressure
Sensor
·Temperature
Sensor
·Pressure Fallback
·Travel Deviation
·Supply Pressure Hi
·Supply Pressure
Lo
·Temperature Hi
·Temperature Lo
·Performance
Critical
·Performance
Reduced
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
Data Type: Bit String
0=inactive
1=active
Indicates what caused an Instrument
Shutdown. Bit remains set even if
condition has passed if Shutdown
Recovery is Manual. All bits are
cleared when MODE_BLK.TARGET is
written. Always enabled whenever
the corresponding
SHUTDOWN_TRIGGER is enabled.
Data Type: Bit String
0=disable
SETUP
1=enable
February 2017