Detailed Setup - Transducer Block
February 2017
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
TASK_1_TYPE
TASK_2_TYPE - TASK_11_TYPE
TASK_1_STATE
TASK_2_STATE - TASK_11_STATE
BATCH_INSIDE_STATUS
TASK_1_STATUS
TASK_2_STATUS -
TASK_11_STATUS
TRIG_CONFIG
TRIG_EVENTS
TRIG_PRE_PTS
TRIG_POST_PTS
TRIG_SAMPLE_INTVL
110
Index
RO /
Mode
Number
RW
•0 - None
•1 - Transducer to MAN
•2 - Transducer to AUTO
•3 - Auto Calibrate
168.2
RO
•4 - Performance Tuner
•5 - Total Scan
•6 - Step Response
•7 - Partial Stroke Test
•8 - Full Stroke Test
168.3 -
RO
See TASK_1_TYPE
168.12
•0x00 - None
•0x01 - Pending
•0x02 - Starting
168.13
RO
•0x03 - Executing
•0x04 - Done
•0x05 - Aborted
•0x06 - Skipped
168.14-
RO
See TASK_1_STATE
168.23
169
RO
•0x00000000 -No Status
•0x0001XXXX - Autocal
Status
•0x0002XXXX -
Performance Tuner
Status
•0x0003XXXX - Total
Scan Status
169.1
RO
•0x0004XXXX - Step
Response Status
•0x0005XXXX - Online
Diag Status
•0x0006XXXX - PST
Status
•0x0007XXXX - FST
Status
169.2 -
RO
See TASK_1_STATUS
169.11
170
Bit 4: PressB Change
Bit 5: PressA Change
Bit 6: Travel Change
Bit 7: Solenoid
Bit 8: Restart
AUTO
Bit 9: External
170.1
MAN
Bit 10: Cutoff
OOS
Bit 11: Air mass flow
Bit 12: Relay crossover
Bit 13: Drive
Bit 14: Travel Deviation
Bit 15: Low Supply
AUTO
170.2
MAN
0 - 600
OOS
AUTO
170.3
MAN
0 - 600
OOS
AUTO
170.4
MAN
0 - 10 sec
OOS
Range
Initial Value
0
600
600
100
Instruction Manual
D103412X012
Protect
Description
Category
Data Type: U8
Data Type: U8
Data Type: U8
Data Type: U8
Data Type: U32
Data Type: U32
Data Type:
SETUP
Data Type: Bit String
SETUP
Data Type: UINT16
SETUP
Data Type: UINT16
Data Type: UINT16
SETUP
Units = msec

Advertisement

Table of Contents
loading