Table 1‐1. Specifications (continued)
Actuator Compatibility
Stem Travel (Sliding‐Stem Linear)
Minimum: 6.35 mm (0.25 inch)
Maximum: 606 mm (23‐7/8 inches)
Shaft Rotation (Quarter‐Turn Rotary)
Minimum: 45_
Maximum: 90_
Weight
DVC6200f
Aluminum: 3.5 kg (7.7 lbs)
Stainless Steel: 8.6 kg (19 lbs)
DVC6205f: 4.1 kg (9 lbs)
DVC6215: 1.4 kg (3.1 lbs)
Construction Materials
Housing, module base and terminal box
Standard: A03600 low copper aluminum alloy
Optional: Stainless steel
Cover: Thermoplastic polyester
Elastomers
Standard: Nitrile
Extreme Temperature: Fluorosilicone
NOTE: Specialized instrument terms are defined in ANSI/ISA Standard 51.1 - Process Instrument Terminology.
1. The pressure/temperature limits in this document and any other applicable code or standard should not be exceeded.
3
2. Normal m
/hour - Normal cubic meters per hour at 0_C and 1.01325 bar, absolute. Scfh - Standard cubic feet per hour at 60_F and 14.7 psia.
3. Values at 1.4 bar (20 psig) based on a single-acting direct relay; values at 5.5 bar (80 psig) based on double-acting relay.
4. Temperature limits vary based on hazardous area approval.
5. Not applicable for travels less than 19 mm (0.75 inch) or for shaft rotation less than 60 degrees. Also not applicable for digital valve controllers in long-stroke applications.
6. M20 electrical connections are only available with ATEX approvals.
7. 4‐conductor shielded cable, 18 to 22 AWG minimum wire size, in rigid or flexible metal conduit, is required for connection between base unit and feedback unit. Pneumatic tubing between base
unit output connection and actuator has been tested to 91 meters (300 feet). At 15 meters (50 feet) there was no performance degradation. At 91 meters there was minimal pneumatic lag.
Table 1‐2. EMC Summary Results—Immunity
Port
Phenomenon
Electrostatic discharge (ESD)
Radiated EM field
Enclosure
Rated power frequency
magnetic field
Burst
Surge
I/O signal/control
Conducted RF
Performance criteria: +/- 1% effect.
1. A = No degradation during testing. B = Temporary degradation during testing, but is self‐recovering.
2. Excluding Simulate function, which meets Performance Criteria B.
Options
J
valves J Integral mounted filter regulator
J
J
Mount
Contact your
office
information.
Declaration of SEP
Fisher Controls International LLC declares this
product to be in compliance with Article 4 paragraph
3 of the PED Directive 2014/68/EU. It was designed
and manufactured in accordance with Sound
Engineering Practice (SEP) and cannot bear the CE
marking related to PED compliance.
However, the product may bear the CE marking to
indicate compliance with other applicable European
Community Directives.
Basic Standard
4 kV contact
IEC 61000‐4‐2
8 kV air
80 to 1000 MHz @ 10V/m with 1 kHz AM at 80%
IEC 61000‐4‐3
1400 to 2000 MHz @ 3V/m with 1 kHz AM at 80%
2000 to 2700 MHz @ 1V/m with 1 kHz AM at 80%
IEC 61000‐4‐8
30 A/m at 50/60 Hz
IEC 61000‐4‐4
1 kV
IEC 61000‐4‐5
1 kV
IEC 61000‐4‐6
150 kHz to 80 MHz at 3 Vrms
DVC6200f Digital Valve Controller
Introduction and Specifications
Supply and output pressure gauges or J Tire
Low‐Bleed Relay J Extreme Temperature
Natural Gas Certified, Single Seal Device J Remote
(7)
J
Stainless Steel
Emerson Automation Solutions sales
or go to www.FIELDVUE.com for additional
Test Level
February 2017
Performance
(1)
Criteria
(2)
A
A
A
(2)
A
B
A
11