Fisher FIELDVUEDVC6200f Instruction Manual page 267

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table E‐13. Input Selector Function Block Parameter Definitions
Label
PARAMETER_NAME
High Alarm
HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Low Alarm
LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Low Low Alarm
LO_LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Output Discrete
OUT_D
Alarm Select
ALM_SEL
Index
Block
RO / RW
Number
Mode
46
46.1
RW
N/A
46.2
RO
N/A
46.3
RO
N/A
46.4
RO
N/A
46.5
RO
N/A
47
47.1
RW
N/A
47.2
RO
N/A
47.3
RO
N/A
47.4
RO
N/A
47.5
RO
N/A
48
48.1
RW
N/A
48.2
RO
N/A
48.3
RO
N/A
48.4
RO
N/A
48.5
RO
N/A
MAN
49
OOS
50
ALL
Range
Initial Value
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
0=Undefined
1=Acknowledged
0
2=
Unacknowledged
0=Undefined
1=Clear reported
2=Clear not reported
0
3=Active reported
4=Active not
reported
0
0
0
Status
Value
0, 1
Status
1: Hi Hi
2: Hi
All Off
3: Lo Lo
4: Lo
DVC6200f Digital Valve Controller
ISEL Function Block
Description
Data Type: DS‐71
The high alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
Data Type: DS‐71
The low alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
Data Type: DS‐71
The low low alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
Data Type: DS‐66
Discrete output to indicate a selected alarm value
Data Type: Bit String
Used to select the process alarm conditions that
will cause the OUT_D parameter to be set.
February 2017
267