Fisher FIELDVUEDVC6200f Instruction Manual page 309

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table E‐35. Discrete Output Function Block Parameter Definitions
Label
PARAMETER_NAME
Simulate Discrete
SIMULATE_D
SIMULATE_STATUS
SIMULATE_VALUE
TRANSDUCER_STATUS
TRANSDUCER_VALUE
ENABLE/DISABLE
Process Value State
PV_STATE
Transducer State
XD_STATE
Grant Deny
GRANT_DENY
GRANT
DENY
I/O Options
IO_OPTS
Status Options
STATUS_OPTS
Readback Discrete
READBACK_D
Cascade Input Discrete
CAS_IN_D
DO Channel
CHANNEL
Index
RO /
Mode
Number
RW
10
10.1
ALL
10.2
ALL
10.3
RO
10.4
RO
0=Not initialized
10.5
ALL
1=Simulation Disabled
2=Simulation Active
11
ALL
12
ALL
13
0: Program
13.1
N/A
1: Tune
2: Alarm
13.2
N/A
3: Local
Valid Bits
0: Invert
1: SP tracks PV in Man
3: SP tracks PV in LO
4: SP Track retained
target in Man or LO
6: Fault State to value
 0: freeze
 1: go to Fault State
14
OOS
value
7: Use Fault State value
on restart
8: Target to Man if Fault
State activated
9: Use PV for
BKCAL_OUT
4: Propagate Failure
15
OOS
Backward
16
RO
N/A
Status
17
ALL
Value
0=undefined
18
OOS
22= Working
Setpoint (D)
Range
Initial Value
Bad
Not Specific
Not Limited
0
Bad
Not Specific
Not Limited
0
1
0
0
All bits: 0
All bits: 0
All bits: 0
0: SP
1: PV
All bits: 0
Dynamic
Bad
Non Specific
Not Limited
0
22= Working
Setpoint (D)
DVC6200f Digital Valve Controller
DO Function Block
Description
Data Type: DS‐83
Allows the transducer discrete input or output
to the block to be manually supplied when
simulate is enabled. When simulation is
disabled, the simulate value and status track the
actual value and status.
Data Type: Uint16
Index to the text describing the states of a
discrete output.
Data Type: Uint16
Index to the text describing the states of a
discrete for the value obtained from the
transducer.
Data Type: DS‐70
Options for controlling access of host
computers and local control panels to
operating, tuning, and alarm parameters of the
block.
GRANT:0=N/A, 1=granted
DENY: 0=N/A, 1=denied
Data Type: Bit String
0=Disable
1=Enable
Allows you to select the type of tracking and the
output value when a fault condition occurs.
Supported I/O options for the DO function block
are SP Tracks PV in Man, SP Tracks PV in LO, SP
Tracks Retained Target in Man or LO, Fault State
to Value, Use Fault state on Restart, Target to
Man if Fault State Activated, and Use PV for
BKCAL_OUT.
Data Type: Bit String
0=Disable
1=Enable
Options the user may select for the block
processing of status.
Data Type: DS‐66
0=closed, 1=open, 5, 10, 15, 30...etc. are
position in 5% increments.
Data Type: DS‐66
The remote set point value from another block.
Data Type: Unsigned16
Defines which transducer parameter receives
the DO output. Select Setpoint (D) to control
valve position.
February 2017
309