Fisher FIELDVUEDVC6200f Instruction Manual page 279

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
266. OS Function Block Parameter List
D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Double indentation and shared Index Number indicates sub‐parameter
Table E‐20. Output Splitter Function Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Setpoint
SP
Output 1
OUT_1
Output 2
OUT_2
Output 1 Range
OUT_1_RANGE
Index
RO /
Block
Number
RW
Mode
1
RO
N/A
0 to 65535
2
RW
ALL
7 bit ASCII
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
7:OOS
5.1
RW
3:AUTO
2:CAS
5.2
RO
5.3
RW
OOS+AUTO+CAS
5.4
RW
1: Block
Configuration Error
7: Input Failure/Bad
6
RO
N/A
PV Status
8: Output Failure
14: Power‐up
15: Out‐of‐Service
7
PV_SCALE +/- 10%
MAN
OUT_SCALE
8
OOS
+/- 10%
MAN
OUT_SCALE
9
OOS
+/- 10%
EU at 100%
EU at 0 %
10
RO
Unit Index
Decimal Point
Range
Initial Value
0
Spaces
0
0
OOS until block
configured, then
last valid target
OOS
OOS AUTO CAS
AUTO+CAS
Dynamic
100
0
%
2
DVC6200f Digital Valve Controller
OS Function Block
Description
Data Type: Unsigned16
The revision level of the static data associated with the
function block. The revision value will be incremented
each time a static parameter value in the block is
changed.
Data Type: Octet String
The user description of the intended application of the
block.
Data Type: Unsigned 16:
The strategy field can be used to identify grouping of
blocks. This data is not checked or processed by the
block.
Data Type: Unsigned8
The identification number of the plant unit. This
information may be used in the host for sorting alarms,
etc.
Data Type: DS‐69
The actual, target, permitted, and normal modes of the
block.
Target: The requested block mode
Actual: The current mode of the block
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String
0
Inactive
=
1
Active
=
This parameter reflects the error status associated with
the hardware or software components associated with
a block. It is a bit string, so that multiple errors may be
shown.
Data Type: DS‐65
Analog setpoint of the block
Data Type: DS‐65
The primary analog output value calculated as a result
of executing the function (the first output value and
status).
Data Type: DS‐65
The primary analog output value calculated as a result
of executing the function (the second output value and
status).
Data Type: DS‐68
The high and low scale values, engineering units code,
and number of decimal places to be used in displaying
the OUT value, this parameter has no effect on this
block.
February 2017
279