DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
D Drive Current Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [83.1]) permits enabling or disabling Self
Test Shutdown for the Drive Current alert. When enabled, and the alert condition is present, the transducer Actual
mode is placed Out of Service. The instrument will attempt to drive the valve to the Zero Power Condition and will
no longer execute transducer control function.
D Drive Current Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [83.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when Drive Current Shutdown clears. If not enabled, the transducer block will remain Out of Service until
power is removed and restored or the user changes the transducer block target mode to Manual or Auto. In any
case, the target mode will remain Out of Service, if the condition that caused the shutdown remains or until the
shutdown trigger is disabled.
D Drive Current Alert Point (DRIVE_CURRENT_ALRT_PT [83.4]) is when the absolute difference between the Drive
Current and Drive Signal exceeds the set threshold for greater than the Drive Current Alert Time.
D Drive Current Alert Time (DRIVE_CURRENT_TIME [83.5]) is the maximum time that the Drive Current Alert Point can
be exceeded before the Drive Current Alert is active.
D Drive Current FD Config
Drive Signal
D Drive Signal (DRIVE_SIGNAL [78]) displays the commanded Drive Signal being sent to the I/P converter as a
percentage of the maximum drive.
The Drive Signal Alert is active if one of the following conditions exist:
Where Zero Power Condition is defined as closed:
Drive Signal < 10% and Calibrated Travel > 3%
Drive Signal > 90% and Calibrated Travel < 97%
Where Zero Power Condition is defined as open:
Drive Signal < 10% and Calibrated Travel < 97%
Drive Signal > 90% and Calibrated Travel > 3%
D Drive Signal FD Config
Processor Impaired
D The Program Memory Alert is active if a pending Flash or NVM failure is present.
D Program Memory Shutdown—The Shutdown Trigger (SHUTDOWN_TRIGGER [83.1]) permits enabling or disabling
Self Test Shutdown. When enabled, and the Program Memory Alert is active, the transducer Actual mode is placed
out of service. The instrument will attempt to drive the valve to the zero power condition and will no longer execute
transducer control function.
D Program Memory Manual Recovery—Shutdown Recovery (SHUTDOWN_RECOVERY [83.2]) permits enabling or
disabling Automatic recovery from Self Test Shutdown. When enabled, the transducer block will return to Target
mode when the condition that caused Program Memory Shutdown clears. If not enabled, the transducer block will
remain Out of Service until power is removed and restored or the user changes the transducer block target mode to
56
Instruction Manual
D103412X012