Fisher FIELDVUEDVC6200f Instruction Manual page 10

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
Introduction and Specifications
February 2017
Table 1‐1. Specifications (continued)
Steady-State Air Consumption
Standard Relay
At 1.4 bar (20 psig) supply pressure:
Less than 0.38 normal m
At 5.5 bar (80 psig) supply pressure:
Less than 1.3 normal m
Low Bleed Relay
At 1.4 bar (20 psig) supply pressure:
Average value 0.056 normal m
At 5.5 bar (80 psig) supply pressure:
Average value 0.184 normal m
Maximum Output Capacity
At 1.4 bar (20 psig) supply pressure:
3
10.0 normal m
/hr (375 scfh)
At 5.5 bar (80 psig) supply pressure:
3
29.5 normal m
/hr (1100 scfh)
Operating Ambient Temperature Limits
-40 to 85_C (-40 to 185_F)
-52 to 85_C (-62 to 185_F) for instruments utilizing
the Extreme Temperature option (fluorosilicone
elastomers)
-52 to 125_C (-62 to 257_F) for remote‐mount
feedback unit
(5)
Independent Linearity
Typical Value: ±0.50% of output span
Electromagnetic Compatibility
Meets EN 61326-1:2013
Immunity—Industrial locations per Table 2 of
the EN 61326-1 standard. Performance is
shown in table 1‐2 below.
Emissions—Class A
ISM equipment rating: Group 1, Class A
Lightning and Surge Protection—The degree of
immunity to lightning is specified as Surge immunity
in table 1‐2. For additional surge protection
commercially available transient protection devices
can be used.
Vibration Testing Method
Tested per ANSI/ISA‐75.13.01 Section 5.3.5. A
resonant frequency search is performed on all three
axes. The instrument is subjected to the ISA specified
1/2 hour endurance test at each major resonance.
10
(2)(3)
3
/hr (14 scfh)
3
/hr (49 scfh)
3
/hr (2.1 scfh)
3
/hr (6.9 scfh)
(2)(3)
(1)(4)
Humidity Testing Method
Tested per IEC 61514-2
Electrical Classification
Hazardous Area Approvals
CSA— Intrinsically Safe, FISCO, Explosion‐proof,
Division 2, Dust Ignition‐proof
FM— Intrinsically Safe, FISCO, Explosion‐proof,
Non‐Incendive, Dust Ignition‐proof
ATEX— Intrinsically Safe, FISCO, Flameproof, Type n,
Dust by intrinsic safety
IECEx— Intrinsically Safe, FISCO, Flameproof, Type n,
Dust by intrinsic safety or by enclosure
Electrical Housing
CSA— Type 4X, IP66
FM— Type 4X, IP66
ATEX— IP66
IECEx— IP66
Other Classifications/Certifications
Natural Gas Certified, Single Seal Device— CSA, FM,
ATEX, and IECEx
Lloyds Register— Marine Type Approval
CUTR— Customs Union Technical Regulations
(Russia, Kazakhstan, Belarus, and Armenia)
INMETRO— National Institute of Metrology, Quality
and Technology (Brazil)
KGS— Korea Gas Safety Corporation (South Korea)
NEPSI— National Supervision and Inspection Centre
for Explosion Protection and Safety of
Instrumentation (China)
PESO CCOE— Petroleum and Explosives Safety
Organisation - Chief Controller of Explosives (India)
TIIS— Technology Institution of Industrial Safety
(Japan)
Contact your
Emerson Automation Solutions sales
office
for classification/certification specific
information
Connections
Supply Pressure: 1/4 NPT internal and integral pad for
mounting 67CFR regulator
Output Pressure: 1/4 NPT internal
Tubing: 3/8‐inch recommended
Vent: 3/8 NPT internal
Electrical: 1/2 NPT internal or M20
-continued-
Instruction Manual
D103412X012
(6)

Advertisement

Table of Contents
loading