Fisher FIELDVUEDVC6200f Instruction Manual page 90

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Drive Current
DRIVE_CURRENT
MLFB
MLFB
INST_ALERTS_ACTIVE
Group 1 Active
GROUP_1_ACTIVE
Group 2 Active
GROUP_2_ACTIVE
90
Index
RO /
Mode
Number
RW
79
RO
N/A
0 to 100%
80
RO
N/A
-100 to 100%
81
Bit 0: Check Alert
Bit 1: Drive Current
Bit 2: Drive Signal
Bit 3: Pending Memory
Fail
Bit 4: Static Memory
Bit 5: I/O Processor
Bit 7: Output Block
Timeout
Bit 8: Blocks to Defaults
Bit 11: Travel Sensor
Bit 12: Port A Pressure
Sensor
Bit 13: Port B Pressure
Sensor
Bit 14: Supply Pressure
81.1
RO
Sensor
Bit 15: Temperature
Sensor
Bit 18: Pressure Fallback
Bit 19: Travel Deviation
Bit 21: Supply Pressure
High
Bit 22: Supply Pressure
Low
Bit 23: Temperature High
Bit 24: Temperature Low
Bit 27: Performance
Critical
Bit 28: Performance
Reduced
Bit 29: Performance Info
Bit 0: Travel Limit Hi Hi
Bit 1: Travel Limit Lo Lo
Bit 2: Travel Limit Hi
Bit 3: Travel Limit Lo
Bit 7: Travel Open
Bit 8: Travel Closed
Bit 9: Proximity Hi Hi
Bit 10: Proximity Hi
Bit 11: Proximity Lo
Bit 12: Proximity Lo Lo
Bit 15: Cycle Counter
Bit 16: Travel
Accumulator
81.2
RO
Bit 18: LCP Comms
Bit 19: LCP Stuck Button
Bit 20: LCP Demand
Button Pressed
Bit 21: Demand Time
Bit 22: Reset Time
Bit 23: Stroke Open Time
Bit 24: Stroke Closed
Time
Bit 25: LCP Reset Button
Pressed
Bit 26: LCP Test Button
Pressed
Range
Initial Value
Dynamic
Dynamic
Instruction Manual
D103412X012
Protect
Description
Category
N/A
Data Type: Float
N/A
Data Type: Float
Data Type: Bit String
0=inactive
1=active
Data Type: Bit String
0=inactive
1=active

Advertisement

Table of Contents
loading