Fisher FIELDVUEDVC6200f Instruction Manual page 105

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
PST_RANDOM_MAX
PST_RETURN_LEAD
PST_AUTO_NEXT_TEST
PST_AUTO_CONFIG
PST_AUTO_ALLOWED_HOURS
PST_AUTO_BLOCKED_START
PST_AUTO_BLOCKED_END
PST_AUTO_ALLOWED_DAYS
PST_AUTO_TYPE
PST_AUTO_ALERT_TIME
PST_AUTO_INFO
PST_AUTO_STATE
PST_AUTO_HOURS_TO_NEXT
Index
RO /
Mode
Number
RW
AUTO
>=0
148
MAN
<=10
OOS
AUTO
>=0
149
MAN
<=100
OOS
AUTO
150
MAN
OOS
151
Zero=0x00000001
One=0x00000002
Two=0x00000004
Three=0x00000008
Four=0x00000010
Five=0x00000020
Six=0x00000040
Seven= 0x00000080
Eight= 0x00000100
Nine=0x00000200
Ten=0x00000400
AUTO
Eleven=0x00000800
MAN
151.1
Twelve=0x00001000
OOS
Thirteen=0x00002000
Fourteen= 0x00004000
Fifteen=0x00008000
Sixteen=0x00010000
Seventeen=0x00020000
Eighteen= 0x00040000
Nineteen= 0x00080000
Twenty=0x00100000
TwentyOne=0x00200000
TwentyTwo=0x00400000
TwentyThree=0x00800000
AUTO
MAN
151.2
OOS
AUTO
151.3
MAN
OOS
0x01 Sunday
0x02 Monday
AUTO
0x04 Tuesday
MAN
151.4
0x08 Wednesday
OOS
0x10 Thursday
0x20 Friday
0x40 Saturday
AUTO
0: Disabled
151.5
MAN
1: Alert Only
OOS
2: Run Tests
AUTO
1516
MAN
> = 0
OOS
152
0: Init
1: Disabled
2: Waiting
152.1
RO
3: Pending
4: Starting
5: Monitoring
152.2
RO
Range
Initial Value
0
1
0
Nine
Ten
Eleven
Twelve
Thirteen
Fourteen
Fifteen
Sixteen
Monday
Tuesday,
Wednesday
Thursday,
Friday
Disabled
96
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
Data Type: Float
SETUP
Units = %
Data Type: Float
SETUP
Units = %
Data Type: FFTime
SETUP
Data Type: Bit String
SETUP
Data Type: FFTime
SETUP
Data Type: FFTime
SETUP
Data Type: Bit String
SETUP
Data Type: ENUM
Data Type: U8
SETUP
Units = Hours
Data Type: Enum
Data Type: Float
February 2017
105

Advertisement

Table of Contents
loading