Fisher FIELDVUEDVC6200f Instruction Manual page 43

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 4‐3. Resource Block Parameter Definitions
Label
PARAMETER_NAME
Failed Suppress
FAILED_MASK
Failed Active
FAILED_ACTIVE
Maintenance Priority
MAINT_PRI
Maintenance Enable
MAINT_ENABLE
Maintenance Suppress
MAINT_MASK
Maintenance Active
MAINT_ACTIVE
Advise Priority
ADVISE_PRI
Advise Enable
ADVISE_ENABLE
Advise Suppress
ADVISE_MASK
Advise Active
ADVISE_ACTIVE
Function Block Options
FB_OPTIONS
Index
RO /
Mode
Number
RW
92
RO
93
RO
AUTO
94
RW
OOS
95
RO
96
RO
97
RO
AUTO
98
RW
OOS
99
RO
100
RO
101
RO
0: AO
1: DO
2: AI
3: DI
102
RO
4: PID
5: ISEL
6: OS
7: MAI
8: CSEL
DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
Initial
Range
Value
Data Type: Bit String, 4 bytes
Copy of FD_FAIL_MASK.
*See FD_FAIL_MASK for Range and Initial Value.
MASK controls whether an alert is reported. If
*
*
alert is enabled the alert condition is evaluated
and the ACTIVE parameter is updated to reflect
if alert is active or not. If the bit is set reporting is
suppressed. Default is all bits cleared.
Data Type: Bit String, 4 bytes
*
*
Copy of FD_FAIL_ACTIVE.
*See FD_FAIL_ACTIVE for Range and Initial Value
0-15
0
Data Type: Uint8
Data Type: Bit String, 4 bytes
Copy of FD_OFFSPEC_MAP.
*
*
*See FD_OFFSPEC_MAP for Range and Initial
Value
Data Type: Bit String, 4 bytes
Copy of FD_OFFSPEC_MASK.
*See FD_OFFSPEC_MASK for Range and Initial
Value
*
*
MASK controls whether an alert is reported. If
alert is enabled the alert condition is evaluated
and the ACTIVE parameter is updated to reflect
if alert is active or not. If the bit is set reporting is
suppressed. Default is all bits cleared.
Data Type: Bit String, 4 bytes
Copy of FD_OFFSPEC_ACTIVE.
*
*
*See FD_OFFSPEC_ACTIVE for Range and Initial
Value
Data Type: Uint8
0-15
0
Data Type: Bit String, 4 bytes
Bit-wise OR of FD_MAINT_MAP and
FD_CHECK_MAP.
*
*
*See FD_MAINT_MAP for Range and
FD_MAINT_MAP and FD_CHECK_MAP for Initial
Value.
Data Type: Bit String, 4 bytes
Bit-wise AND of FD_MAINT_MASK and
FD_CHECK_MASK. *See FD_MAINT_MASK and
FD_CHECK_MASK for Range and Initial Value.
*
*
MASK controls whether an alert is reported. If
alert is enabled the alert condition is evaluated
and the ACTIVE parameter is updated to reflect
if alert is active or not. If the bit is set reporting is
suppressed. Default is all bits cleared.
Data Type: Bit String, 4 bytes
Bit-wise OR of FD_MAINT_ACTIVE and
*
*
FD_CHECK_ACTIVE. *See FD_MAINT_ACTIVE or
FD_CHECK_ACTIVE for Range.
Data Type: Bit String, 4 bytes
0 = disabled
1 = enabled
Indicates which function block licensing options
are enabled. One bit for each block type that is
supported. Unlicensed blocks cannot be
scheduled and the Actual block mode will
remain OOS.
February 2017
Description
43