Fisher FIELDVUEDVC6200f Instruction Manual page 133

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Stroking the Digital Valve Controller Output
Stroke Valve is used to confirm proper valve operation. Follow the prompts on the Field Communicator display to
select from the following: Done, Ramp Open, Ramp Closed, Ramp to Target, Step to Target, and Stop.
•Done—Select this if you are done. All ramping is stopped when DONE is selected.
•Ramp Open—ramps the travel toward open at the rate of 1.0% per second of the ranged travel.
•Ramp Closed—ramps the travel toward closed at the rate of 1.0% per second of the ranged travel.
•Ramp to Target—ramps the travel to the specified target at the rate of 1.0% per second of the ranged travel.
•Step to Target—steps the travel to the specified target.
•Stop—stops the command.
Trend
Trend chart of Setpoint (WORKING_SP.VALUE [20.2]), Travel (WORKING_POS.VALUE [19.2]), and Supply Pressure
(SUPPLY_PRESSURE.VALUE [61.2]).
PST/FST
Partial Stroke Test
Travel (WORKING_POS.VALUE [19.2])
Travel Status (WORKING_POS.STATUS[19.1])
Last Successful PST
•Time Since Last PST Successful (PST_TIME_OF_LAST_SUCCESS [130.1])
•Last Successful PST (SST_SUCCESS [131.1])
•Time Since Last FST Successful (FST_TIME_OF_LAST_SUCCESS [130.2])
•Last Successful FST (FST_SUCCESS [131.2])
PST/FST Info
•PST Calibrated Travel (PST_CAL_TRAVEL [153])
•PST Min Travel (PST_STRK_TRAV [141])
•PST Max Travel (PST_MAX_TRAVEL [145])
•Set Point Overdrive (PST_OVERDRIVE_AMT[144])
•Test Pause Time (VST_PAUSE [120])
DVC6200f Digital Valve Controller
Viewing Device Variables and Diagnostics
February 2017
133