DVC6200f Digital Valve Controller
PID Function Block
February 2017
Table E‐6. PID Function Block System Parameters Definitions
Label
PARAMETER_NAME
Low Low Alarm
LO_LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Deviation High Alarm
DV_HI_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Deviation Low Alarm
DV_LO_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
Bias
BIAS
Error
ERROR
SP Work
SP_WRK
SP FTime
SP_FTIME
Math Form
MATHFORM
236
Index
RO /
Block
Number
RW
Mode
63
0=Undefined
63.1
RW
N/A
1=Acknowledged
2=
0=Undefined
1=Clear reported
63.2
RO
N/A
2=Clear not reported
3=Active reported
4=Active not reported
63.3
RO
N/A
63.4
RO
N/A
63.5
RO
N/A
64
0=Undefined
64.1
RW
N/A
1=Acknowledged
2=
0=Undefined
1=Clear reported
2=Clear not reported
64.2
RO
N/A
3=Active reported
4=Active not reported
64.3
RO
N/A
64.4
RO
N/A
64.5
RO
N/A
65
0=Undefined
65.1
RW
N/A
1=Acknowledged
2=
0=Undefined
1=Clear reported
65.2
RO
N/A
2=Clear not reported
3=Active reported
4=Active not reported
65.3
RO
N/A
65.4
RO
N/A
65.5
RO
N/A
66
ALL
OUT_SCALE +/- 10%
67
RO
N/A
68
RO
N/A
69
ALL
Positive
0=Standard
70
OOS
1=Series
Range
Initial Value
0=undefined
Unacknowledged
0=undefined
0=undefined
Unacknowledged
0=undefined
0=undefined
Unacknowledged
0=undefined
Extended Parameters
Dynamic
Dynamic
0=Standard
Instruction Manual
Description
Data Type: DS‐71
The LO LO alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float
0
0
0
Data Type: DS‐71
The DV HI alarm data, which includes a value of the
alarm, a timestamp of occurrence, and the state of
the alarm.
VALUE Data Type: Float
0
0
0
Data Type: DS‐71
The DV LO alarm data, which includes a value of
the alarm, a timestamp of occurrence, and the
state of the alarm.
VALUE Data Type: Float
0
0
0
Data Type: Float
The bias value used to calculate output for a PD
0
structure.
Data Type: Float
The error (SP-PV) used to determine the control
action.
Data Type: Float
The working set point of the block after limiting
and filtering is applied. EU of PV_SCALE
Data Type: Float
The time constant of the first‐order SP filter. It is
0
the time, in seconds, required for a 63 percent
change in the IN value. Applied after SP rate
limiting.
Data Type: Unsigned8
Selects equation form (series or standard)
D103412X012

Advertisement

Table of Contents
loading