TVL_PRESS_RATE_FILT
PRESS_CAL
Supply Pressure Scale
SUPP_PRESS_SCALE
Supply Pressure Offset
SUPP_PRESS_OFFSET
Pressure A Scale
PRESS_A_SCALE
Pressure A Offset
PRESS_A_OFFSET
Pressure B Scale
PRESS_B_SCALE
Pressure B Offset
PRESS_B_OFFSET
PRESS_TUNE
Pressure Cutoff Hi
PRESS_CUTOFF_HI
Pressure Cutoff Lo
PRESS_CUTOFF_LO
Pressure Proportional Gain
PRESS_PROP_GAIN
Pressure Integral Gain
PRESS_INTEG_GAIN
Pressure Rate Gain
PRESS_RATE_GAIN
Pressure Integral Dead Zone
PRESS_INTEG_DEADZ
Pressure Integral Limit Hi
PRESS_INTEG_HI_LIM
Pressure Integral Limit Lo
PRESS_INTEG_LO_LIM
Pressure Integral IC Hi
PRESS_INTEG_IC_HI
Pressure Integral IC Lo
PRESS_INTEG_IC_LO
Pressure MLFB Gain
PRESS_MLFB_GAIN
Temperature
TEMPERATURE
Input Characterization
INPUT_CHAR
Custom Points
CUSTOM_POINTS
Drive Signal
DRIVE_SIGNAL
Index
RO /
Mode
Number
RW
72.10
0 - 1
73
MAN
73.1
RW
> 0
OOS
MAN
73.2
RW
0 to 16383
OOS
MAN
73.3
RW
> 0
OOS
MAN
734
RW
0 to 16383
OOS
MAN
73.5
RW
> 0
OOS
MAN
73.6
RW
0 to 16383
OOS
74
MAN
74.1
RW
-25 to 125
OOS
MAN
74.2
RW
-25 to 125
OOS
MAN
74.3
RW
>=0, <32
OOS
MAN
74.4
RW
>=0, <32
OOS
MAN
74.5
RW
>=0, <=512
OOS
MAN
74.6
RW
>=0, <=2
OOS
MAN
74.7
RW
>=0, <=100
OOS
MAN
74.8
RW
<=0, >=-100
OOS
MAN
74.9
RW
>=-100, <=100
OOS
MAN
74.10
RW
>=-100, <=100
OOS
MAN
74.11
RW
>0, <=100
OOS
75
RO
1 = Linear
2 = Equal %
MAN
3 = Quick Opening
76
OOS
4 = Reserved
5 = Custom
-2500 to 12500,
excursions permitted,
Each X value must be >
previous value, each Y
77
value must be > previous
value. Checked when
CHARACTERIZATION
changed to CUSTOM.
78
RO
N/A
0 to 100%
Range
Initial Value
99.5%
0.5%
2.2
0.1
0
0.25%
50%
-50%
12%
-12%
35
Linear
1st pt = 0,0
2nd pt = 100,100
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
SETUP
Data Type: Float
CAL
Data Type: Float
CAL
Data Type: Float
CAL
Data Type: UINT16
CAL
Data Type: Float
CAL
Data Type: Float
CAL
Data Type: Float
SETUP
Data Type: Float
SETUP
Data Type: Float
Data Type: Float
SETUP
Proportional gain
Data Type: Float
SETUP
Integral resets per second
Data Type: Float
SETUP
Derivative gain
Data Type: Float
SETUP
Integrator Deadzone, 1/2 width
Data Type: Float
SETUP
Integrator limits
Data Type: Float
SETUP
Integrator limits
SETUP
Data Type: Float
SETUP
Data Type: Float
SETUP
Data Type: Float
Data Type: Float
Electronics temperature - Controls
AI channel 11
SETUP
Data Type: UINT8
Data Type: INT16 Array[43]
Each item - 2500 to 12500
First integrator is number of valid
points. Followed by up to 21 X
values and then 21 Y values.
SETUP
X values must be increasing.
Y values must be increasing or same.
A value of 2050 represent 20.50%
Custom Points can be written only if
Input Characterization
(INPUT_CHAR [50]) is not custom.
Data Type: Float
N/A
Controls AI channel 9
February 2017
89