Fisher FIELDVUEDVC6200f Instruction Manual page 217

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table E‐2. Analog Output Function Block Parameter Definitions
Label
PARAMETER_NAME
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Process Variable
PV
Set Point
SP
Output
OUT
Simulate
SIMULATE
SIMULATE_STATUS
SIMULATE_VALUE
TRANSDUCER_STATUS
TRANSDUCER_VALUE
ENABLE/DISABLE
Process Value Scale
PV_SCALE
Transducer Scale
XD_SCALE
Index
RO /
Block
Number
RW
Mode
5
OOS
MAN
AUTO
5.1
RW
ALL
AUTO‐CAS
AUTO‐RCAS
5.2
RO
ALL
OOS+MAN+AUTO+
5.3
RW
ALL
CAS+RCAS
5.4
RW
ALL
1: Block Configuration
Error
3: Simulate Active
4: Local Override
6
RO
N/A
5: Device Fault State Set
8: Output Failure
14: Power‐up
15: Out‐of‐Service
PV Status set equal to
7
RO
N/A
READBACK status
OOS
MAN
8
PV_SCALE +/- 10%
AUTO
MAN
9
OUT_SCALE +/- 10%
OOS
10
10.1
RW
ALL
10.2
RW
ALL
10.3
RO
ALL
10.4
RO
ALL
0: Not Initialized
1: Simulation Disable
10.5
RW
ALL
2: Simulation Active
EU at 100%
EU at 0%
11
RW
OOS
Units index
Decimal Point
EU at 100%
EU at 0%
12
RO
OOS
Units index
Decimal Point
DVC6200f Digital Valve Controller
Range
Initial Value
OOS until
block is
configured,
then last valid
target
OOS
OOS+MAN+
AUTO+
CAS+RCAS
CAS+AUTO
Dynamic
Dynamic
Dynamic
Dynamic
0
0
0
0
1: Simulation
Disabled
100
0
%
0
100
0
%
0
AO Function Block
February 2017
Description
Data Type: DS‐69
Valid Bits: 7: OOS, 6: IMAN, 5: LO, 4: MAN, 3: AUTO,
2: CAS, 1: RCAS
The actual, target, permitted, and normal modes of
the block.
Target: The requested block mode
Actual: The current mode of the block
(Note: Bit 6 (IMAN) is valid for ACTUAL only)
Permitted: Allowed modes for Target
Normal: Most common mode for Target
Data Type: Bit String (2 byte)
0=inactive
1=active
This parameter reflects the error status associated
with the hardware or software components
associated with a block. It is a bit string, so that
multiple errors may be shown. See table E‐1.
Data Type: DS‐65
The process variable used in block execution. This
value is converted from READBACK to show the
actuator position in the same units as the setpoint
value.
Data Type: DS‐65
The SP of the analog block. Can be derived from
CAS_IN, RCAS_IN in normal modes, or can track PV
in MAN, IMan or LO modes. IO_OPTS is used to
determine value of SP in MAN, IMan or LO. If no
IO_OPTS for SP tracking are set, SP will freeze when
mode changes from CAS or RCAS.
Data Type: DS‐65
The primary value and status calculated by the
block in Auto mode. OUT may be set manually in
Man mode.
Data Type: DS‐82
Allows the analog input to be manually supplied
when simulate is enabled. When simulation is
disabled, the simulate value and status track actual
value & status.
Data Type: DS‐68
The high and low scale values, engineering units
code, and number of decimal places to be used in
displaying the PV parameter and parameters which
have the same scaling as PV.
Data Type: DS‐68
The high and low scale values and engineering
units code are read only. This parameter
determines the number of digits to the right of the
decimal point used with the value obtained from
the transducer for a specified channel.
217