DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
February 2017
Table 4‐3. Resource Block Parameter Definitions
Label
PARAMETER_NAME
Write Priority
WRITE_PRI
Write Alarm
WRITE_ALM
UNACKNOWLEDGED
ALARM_STATE
TIME_STAMP
SUBCODE
VALUE
ITK Version
ITK_VER
Not used
FD_VER
FD_FAIL_ACTIVE
38
Index
RO /
Mode
Number
RW
39
RW
ALL
0 to 15
40
0: Uninitialized
40.1
RW
ALL
1: Acknowledged
2: Unacknowledged
0: Uninitialized
1: Clear-reported
40.2
RO
NA
2: Clear-not reported
3: Active-reported
4: Active-not reported
40.3
RO
NA
40.4
RO
NA
40.5
RO
NA
41
RO
N/A
Extended Parameters
42-51
RO
52
RO
0: Check
1: Drive Current
2: Drive Signal
3: Processor Impaired
4: LCP Button Pressed
5: LCP
Communications Lost
6: Travel Sensor Fail
7: Outlet Pressure
Sensor Fail
8: Supply Pressure
Sensor Fail
9: Temperature
Sensor Fail
10: Supply Pressure
53
RO
11: Temperature Limit
12: Travel Deviation
13: Travel/Setpoint
Limit
14: Movement History
16: Performance
Critical
17: Performance
Reduced
18: Performance Info
19: Latch Active
20: Pressure Fallback
23: PST Pass
24: PST Abnormal
Continued on next
page:
Initial
Range
Value
Data Type: Unsigned8
Priority of the alarm generated by setting
WRITE_LOCK to Unlocked.
0
Data Type: DS‐72
This alarm is generated when Unlocked in the
WRITE_LOCK parameter is set. This alarm has a
Dynamic
priority of WRITE_PRI. For a WRITE_ALM to be
broadcast to the host the following conditions
must be met:
Dynamic
setup
Dynamic
for Write Alarm must be clear.
Dynamic
Dynamic
Data Type: Unsigned16
Major version of ITK test this device has been
*
tested to. *Initial value depends on the revision
of the DVC6200f.
1
Data Type: Uint16
Data Type: Bit String, 4 bytes
Alert is the act of detecting a condition in the
dev device.
0 = Inactive
1 = Active
Instruction Manual
D103412X012
Description
0 -- Clear associated alert
1 -- Associated alert not sent
2 -- Reserved for alerts that do not require the
attention of a plant operator, e.g. diagnostic
and system alerts
3-7 -- advisory alarms
8-15 -- critical alarms
The feature Reports must be selected
Alert communication with the host must be
In the ALARM_SUM parameter, the disable bit
WRITE_PRI must be greater than 1.