DVC6200f Digital Valve Controller
Detailed Setup - Resource Block
February 2017
Block Alarm Auto Acknowledge (ACK_OPTION [38]) determines if the block alarm will be automatically
acknowledged.
Discrete Alarm Disabled The Write Alarm (WRITE_ALM [40]) is used to alert when parameters are writable to the
device. Alarm Summary (ALARM_SUM [37]) determines if the Discrete Alarm is disabled.
Discrete Alarm Auto Acknowledge (ACK_OPTION [38]) determines if the Write Alarm associated with the block will be
automatically acknowledged.

Identification

Device ID (DEVICE_ID [110]) is the 32 character Device ID.
Electronics Serial Number (ELECTRONICS_SN [106]) is set at the factory.
Factory Serial Number (FACTORY_SN [107]) is the instrument serial number set at the factory.
Field Serial Number (FIELD_SN [108]) is the serial number of instrument assigned in field.
Tag Description (TAG_DESC [2]) is used to assign a unique 32 character description to each block within the digital
valve controller to describe the intended application for the block.
Strategy (STRATEGY [3]) permits strategic grouping of blocks so the operator can identify where the block is located.
The blocks may be grouped by plant area, plant equipment, etc. Enter a value between 0 and 65535 in the Strategy
field.
Manufacturer (MANUFAC_ID [10]) identifies the manufacturer of the instrument. It is used by the host system to
locate the DD file for the device. For Fisher the Manufacturer ID is 0x5100.
Device Type (DEV_TYPE [11]) identifies the type of device. It is used by the host system to locate the DD file for the
device. For a DVC6200f digital valve controller the device type is 0x4602.
Diagnostic Options (DIAG_OPTIONS [45]) shows the diagnostic options available in the instrument.
26
Instruction Manual
D103412X012