DVC6200f Digital Valve Controller
OS Function Block
February 2017
drop the good downstream block out of Cas mode for one evaluation cycle and then restore Cas mode. This initializes
the upstream controller to the remaining good region of control.
Block Errors
Table E‐19 lists conditions reported in the BLOCK_ERR [6] parameter.
Table E‐19. OS BLOCK_ERR Conditions
Condition Number
1
Block Configuration Error—SHED_OPT or BYPASS set to 0
7
Input failure/process variable has Bad status—The parameter linked to IN is indicating a Bad status.
8
Output Failure
14
Power Up
15
Out of Service—The actual mode is Out of Service (OOS).
278
‐ Set if OUT quality is bad and the Actual mode is not Out of Service.
- Set if the Target mode is Out of Service when powered up until the mode is changed.
Condition Name and Description
Instruction Manual
D103412X012