D103412X012
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
VST_COMMAND
VST_MODE
VST_PAUSE
VST_RESULT
VST_DETAILED_RESULT
VST_SAMPLE_INT
VST_ABORT_MODE
VST_INFO
VST_STATE
Index
RO /
Mode
Number
RW
0: Un-initialized
1: Execute VST (store as
reference)
2: Execute VST (store as
current)
3: Abort stroke test
4: Reset VST_RESULT to
'no initial result'
8: Execute PST
9: Execute FST
10: Execute PST w/ Host
AUTO
Timeout
118
MAN
11: Execute FST w/ Host
OOS
Timeout
12: Execute Valve
Signature
13: Execute Step
Response
14: End Wait
15: Execute Online
Capture
16: Execute FST w/
cutoffs/char/rate-limits
128: Host Present
AUTO
0: Disable
119
MAN
1: PST for ESD valves
OOS
2: FST for ESD valves
AUTO
MAN
120
OOS
0: No initial results
121
RO
1: Last VST successful
2: Last VST abnormal
0: Test command
rejected
1: Time Limit Exceeded
2: Press Limit Exceeded
3: Friction Limit Exceeded
4: PST Travel Limit
Exceeded
5: Overridden (abort due
122
RO
to external event)
6-7: Reserved
8: Travel/Pressure
Control Changed
9: No Movement
10: No Return
11: Shutdown
12: Sensor Fail
123
ALL
0-5000
0: Ramp
124
ALL
1: Step
125
0: Not Running
1: Checking Conditions
2: Finding Storage
3: Freeing Storage
4: Starting
125.1
RO
5: Running
6: Cancelling
7: Demand
8: End
Range
Initial Value
0
0
5
100
Ramp
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
NONE
Data Type: UINT8
SETUP
Data Type: UINT8
Data Type: Float
SETUP
Units = Seconds
Data Type: UINT8
Data Type: Bit String
Data Type: UINT16
SETUP
Units = msec
SETUP
Data Type: UINT8
Data Type: UINT8
February 2017