Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Table 1‐1. Specifications
Available Mounting
DVC6200f digital valve controller and DVC6215
feedback unit: J Integral mounting to 657/667 or
GX actuators J Integral mounting to Fisher rotary
actuators, J Sliding‐stem linear applications
J
Quarter‐turn rotary applications
DVC6205f base unit for 2 inch pipestand or wall
mounting (for remote-mount)
The DVC6200f digital valve controller or DVC6215
feedback unit can also be mounted on other
actuators that comply with IEC 60534-6-1, IEC
60534-6-2, VDI/VDE 3845 and NAMUR mounting
standards.
Instrument Blocks
Resource Block
Transducer Block complies with F
specification FF-906 for valve stroke testing
Function Block Suites
J Standard Control (throttling control)
Includes AO, PID, CSEL, ISEL, OS, AI, MAI, DO,
and DI function block
J Fieldbus Control (throttling control)
Contains the AO function block
J Fieldbus Logic [discrete (on/off) connectivity]
Includes DO, and DI function blocks
Function Block Instantiation
If a host system supports block instantiation, a
maximum of 20 function blocks can be instantiated in
the device at any given time from the available
function blocks, which may include AO (1), DO (1), AI
(4), DI (6), MAI (1), PID (4), OS (3), ISEL (2), CSEL (2)
Note: Only the function blocks available in the
function block suite can be instantiated by the host
system
Block Execution Times
AO Block: 20 ms
PID Block: 20 ms
ISEL Block: 20 ms
OS Block: 20 ms
AI Block: 20 ms
Fieldbus
OUNDATION
MAI BLock: 35 ms
DO Block: 20 ms
DI Block: 15 ms
CSEL Block: 15 ms
Electrical Input
Voltage Level: 9 to 32 volts
Maximum Current: 19 mA
Reverse Polarity Protection: Unit is not polarity
sensitive
Termination: Bus must be properly terminated per
ISA SP50 guidelines
Digital Communication Protocol
F
fieldbus registered device
OUNDATION
Physical Layer Type(s):
121—Low-power signaling, bus‐powered,
Entity Model I.S.
511—Low-power signaling, bus‐powered, FISCO I.S.
Fieldbus Device Capabilities
Backup Link Master capable
Supply Pressure
Minimum Recommended: 0.3 bar (5 psig) higher
than maximum actuator requirements
Maximum: 10.0 bar (145 psig) or maximum pressure
rating of the actuator, whichever is lower
Medium: Air or Natural Gas
Supply medium must be clean, dry and noncorrosive
Per ISA Standard 7.0.01
A maximum 40 micrometer particle size in the air
system is acceptable. Further filtration down to
5 micrometer particle size is recommended.
Lubricant content is not to exceed 1 ppm weight
(w/w) or volume (v/v) basis. Condensation in the air
supply should be minimized.
Per ISO 8573-1
Maximum particle density size: Class 7
Oil content: Class 3
Pressure Dew Point: Class 3 or at least 10_C less than
the lowest ambient temperature expected
Output Signal
Pneumatic signal, up to full supply pressure
Minimum Span: 0.4 bar (6 psig)
Maximum Span: 9.5 bar (140 psig)
Action: J Double, J Single Direct or J Reverse
-continued-
DVC6200f Digital Valve Controller
Introduction and Specifications
(1)
February 2017
9