Performance Alerts

Note
Performance Alerts are only available with a PD or a PST instrument. Additionally, for the PD alerts to function properly:
D
The transducer block mode must not be out of service.
D
The travel/pressure control state must be in travel control mode, and
D
Bench Set Hi, Bench Set Lo, and Nominal Supply Pressure must be set in the Spec Sheets, then enable the Performance
Information instrument alert (PD_COMMAND [105.1]).
PD Inside Status shows the status of Performance Diagnostics.
PD Run enables or disables Performance Diagnostics in the instrument (PD Inside). Selecting PD Off disables PD Inside.
Selecting PD On enables PD Inside.
Performance Critical
D The Performance Critical Alert is active if the instrument is no longer able to control the valve or performance has
been dramatically reduced.
D Performance Critical FD Config
Performance Reduced
D The Performance Reduced Alert is active if the instrument has detected a reduction in performance.
D Performance Reduced FD Config
Performance Information
D The Performance Information Alert is active if the instrument has detected a condition that may pertain to control
performance.
D Performance Information FD Config

FST/PST Alerts

PST Abnormal
D PST Abnormal Alert
D PST Abnormal FD Config
PST Pass
D PST Pass Alert
D PST Pass FD Config