Fisher FIELDVUEDVC6200f Instruction Manual page 63

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012
Figure 4‐4. Cycle Counter Deadband (set at 10%)
Deadband exceeded, and direction
changed, new Reference Point
established
Deadband Reference
Point
Deadband (+/- 5%)
A6533‐1
Travel Accumulator
D Travel Accumulator (TRAVEL_ACCUM [29]) records the total change in travel, in percent (%) of ranged travel, since
the accumulator was last cleared. The value of the Travel Accumulator increments when the magnitude of the
change exceeds the Travel Accumulator Dead‐band. See figure 4‐5. You can reset the Travel Accumulator by
configuring it to zero.
D The Travel Accumulator Alert is active if the Travel Accumulator exceeds the Travel Accumulator Alert Point. The
Travel Accumulator Alert is set when the Travel Accumulator value exceeds the Travel Accumulator Alert Point. It is
cleared after you reset the Travel Accumulation to a value less than the alert point.
D Travel Accumulator Alert Point (TVL_ACCUM_ALRT_PT [84.2]) is the value of the Travel Accumulator, in percent (%)
of ranged travel, which, when exceeded, sets the Travel Accumulator Alert.
D Travel Accumulator Deadband (TVL_ACCUM_DB [84.3]) is the area around the travel reference point, in percent (%)
of ranged travel, that was established at the last increment of the accumulator. This area must be exceeded before
a change in travel can be accumulated. See figure 4‐5.
D Movement History FD Config
Diagnostic in Progress
D Diagnostic in Progress Alert
D Diagnostic in Progress FD Config
Point at which
cycle is counted
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
63