Transducer Block Parameter List - Fisher FIELDVUEDVC6200f Instruction Manual

Digital valve controller for foundation fieldbus
Table of Contents

Advertisement

Instruction Manual
D103412X012

Transducer Block Parameter List

D Read/Write Capability: RO - Read Only, RW - Read Write
D Mode: The block mode(s) required to write to the parameter
D Protection Category: Indicates whether or not the parameter is writable while the PROTECTION parameter
 is set to a particular level.
-N/A indicates a read‐only parameter that is never writable, regardless of the value of the PROTECTION parameter
-NONE indicates a read‐only parameter that is always writable, regardless of the value of the PROTECTION parameter
-CAL indicates a parameter that is only writable while the value of the PROTECTION parameter is "NONE".
-SETUP indicates a parameter that is only writable while the value of the PROTECTION parameter is "NONE" or "CAL".
-ALL indicates a parameter that is writable while the value of the PROTECTION parameter is "NONE", "CAL", or "SETUP & CAL".
Table 4‐12. Transducer Block Parameter Definitions
Label
PARAMETER_NAME
Static Revision
ST_REV
Tag Description
TAG_DESC
Strategy
STRATEGY
Alert Key
ALERT_KEY
Block Mode
MODE_BLK
TARGET
ACTUAL
PERMITTED
NORMAL
Block Error
BLOCK_ERR
Update Event
UPDATE_EVT
UNACKNOWLEDGED
Index
RO /
Mode
Number
RW
1
RO
N/A
0 to 65535
2
RW
ALL
3
RW
ALL
0 to 65535
4
RW
ALL
1 to 255
5
3: AUTO
5.1
RW
ALL
4: MAN
7: OOS
3: AUTO
5.2
RO
N/A
4: MAN
7: OOS
3: AUTO
4: MAN
5.3
RW
ALL
5: LO
7: OOS
3: AUTO
4: MAN
5.4
RW
ALL
7: OOS
1: Configuration Error
6
RO
N/A
15: Out‐of‐Service
7
0: Uninitialized
1: Acknowledged
7.1
RW
ALL
2: Unacknowledged
Range
Initial Value
0
Spaces
0
0
OOS
N/A
AUTO+MAN+OOS
3:AUTO
Dynamic
0
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
Protect
Description
Category
Data Type: Uint16
The revision level of the static data.
Increments by one each time a static
N/A
parameter is written. The value is
reset to 0 whenever a Restart with
Defaults is performed. See
Restarting the Instrument.
Data Type: String
SETUP
The description of the block.
Data Type: Uint16
SETUP
Used to help group blocks.
Data Type: Uint8
The identification number of the
plant unit. Devices in a loop or plant
SETUP
section can be assigned with a
common alert key to aid the
operator in determining location of
alerts.
Data Type: DS‐69
NONE
The actual, target, permitted, and
normal modes.
Target: The requested block mode
N/A
Actual: The current mode of
the block
Permitted: Allowed modes for
Target
NONE
Normal: Most common mode
for Target
NONE
Data Type: Bit String (2 byte)
Error status associated with
N/A
hardware or firmware for the
transducer block.
NONE
February 2017
79