Instruction Manual
D103412X012
Pressure Fallback
D The Pressure Fallback Alert is active if a travel sensor failure or a gross travel deviation has resulted in fallback to
pressure control.
D Pressure Fallback FD Config
Temperature Sensor
D The Temperature Sensor Alert is active if the Temperature Sensor reading is outside the functional range.
D Temperature Sensor FD Config

Environment Alerts

Supply Pressure
D Supply (SUPPLY_PRESSURE.VALUE [61.2]) displays the instrument supply pressure in kPa, bar, or psi.
D The Supply Pressure High Alert is active when the supply pressure exceeds the Supply Pressure High Alert Point.
D Supply Pressure High Alert Point (SUP_PRES_HI_ALRT_PT [83.3])—The Supply Pressure High Alert is active when
supply pressure exceeds the Supply Pressure High Alert Point.
D The Supply Pressure Low Alert is active when the supply pressure is lower than the Supply Pressure Low Alert Point.
D Supply Pressure Low Alert Point (SUP_PRES_LO_ALRT_PT [83.9])— When the supply pressure falls below the supply
pressure alert point, the supply pressure low alert is active. To disable the supply pressure alert, set Supply Pressure
Alert Point to zero.
D Supply Pressure FD Config
Temperature Limit
D Temperature (TEMPERATURE [75]), in Degrees Fahrenheit or Celsius. The temperature is measured from a sensor
mounted on the digital valve controller's printed wiring board.
D The Temperature High Alert is active if the temperature is greater than the Temperature High Alert Point.
D Temperature High Alert Point (TEMP_HI_ALRT_PT [83.6])—The Temperature High Alert is active when the
instrument temperature exceeds the Temperature High Alert Point.
D The Temperature Low Alert is active if the temperature is lower than the Temperature Low Alert Point.
D Temperature Low Alert Point (TEMP_LO_ALRT_PT [83.7])— The Temperature Low Alert is active when the
instrument temperature is lower than the Temperature Low Alert Point.
D Temperature Limit FD Config
DVC6200f Digital Valve Controller
Detailed Setup - Transducer Block
February 2017
59