B.3 Parameter Table
H4: Analog Outputs
No.(Addr.)
Name
H4-01
Terminal FM Monitor Selection
(41DH)
H4-02
(41EH)
Terminal FM Gain
H4-03
(41FH)
Terminal FM Bias
H4-04
Terminal AM Monitor Selection
(420H)
H4-05
(421H)
Terminal AM Gain
H4-06
(422H)
Terminal AM Bias
H4-07
Terminal FM Signal Level
(423H)
Selection
H4-08
Terminal AM Signal Level
(424H)
Selection
H5: MEMOBUS/Modbus Serial Communication
Note: The settings for MEMOBUS/Modbus communications become effective when the drive is restarted.
No.(Addr.)
Name
H5-01
(425H)
Drive Node Address
<14>
H5-02
Communication Speed Selection
(426H)
H5-03
Communication Parity Selection
(427H)
H5-04
Stopping Method After
(428H)
Communication Error (CE)
H5-05
Communication Fault Detection
(429H)
Selection
414
All Modes
Selects the data to be output through multi-function analog output terminal FM.
Set the desired monitor parameter to the digits available in U-. For example, enter "103"
for U1-03.
All Modes
Sets the signal level at terminal FM that is equal to 100% of the selected monitor value.
All Modes
Sets the bias value added to the terminal FM output signal.
All Modes
Selects the data to be output through multi-function analog output terminal AM.
Set the desired monitor parameter to the digits available in U-. For example, enter "103"
for U1-03.
All Modes
Sets the signal level at terminal AM that is equal to 100% of the selected monitor value.
All Modes
Sets the bias value added to the terminal AM output signal.
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
0: 0 to 10 V
1: -10 to 10 V
All Modes
Selects drive station node number (address) for MEMOBUS/Modbus terminals R+, R-, S+, S-.
Cycle power for the setting to take effect.
All Modes
0: 1200 bps
1: 2400 bps
2: 4800 bps
3: 9600 bps
4: 19200 bps
5: 38400 bps
6: 57600 bps
7: 76800 bps
8: 115200 bps
Cycle power for the setting to take effect.
All Modes
0: No parity
1: Even parity
2: Odd parity
Cycle power for the setting to take effect.
All Modes
0: Ramp to stop
1: Coast to stop
2: Fast Stop
3: Alarm only
All Modes
0: Disabled
1: Enabled. If communication is lost for more than two seconds, a CE fault will occur.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Description
Description
Setting
common_
TMonly
Default: 102
Min: 000
Max: 999
Default: 100.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
TMonly
Default: 103
Min: 000
Max: 999
Default: 50.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
Default: 0.0%
common_
TMonly
Min: -999.9%
Max: 999.9%
common_
Default: 0
TMonly
Min: 0
Max: 1
common_
Default: 0
TMonly
Min: 0
Max: 1
Setting
common_
Default: 1
TMonly
Min: 0
Max: FF
common_
TMonly
Default: 3
Min: 0
Max: 8
common_
TMonly
Default: 0
Min: 0
Max: 2
common_
TMonly
Default: 3
Min: 0
Max: 3
common_
Default: 1
TMonly
Min: 0
Max: 1
Page
220
221
221
220
221
221
222
222
Page
448
448
448
449
449