C.9 MEMOBUS/Modbus Data Table
Register No.
Communications Error Contents
bit 0
bit 1
bit 2
003DH
bit 3
bit 4
bit 5
bit 6
bit 7 to bit F
003EH
Output Speed
003FH
0040H to 004AH
Used for various monitors U1-.
Drive Status (U1-12)
bit 0
bit 1
bit 2
bit 3
bit 4
bit 5
004BH
bit 6
bit 7
bit 8
bit 9
bit A
bit B to D
bit E
bit F
004CH to 007EH
Used for various monitors U1-, U4-, and U6-.
007FH
Alarm Code,
Used for monitors U2-, U3-.
0080H to 0097H
value descriptions.
U4-01 (Cumulative Operation Time)
0098H, 0099H
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
U4-03 (Cooling Fan Operation Time)
009AH, 009BH
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
009CH to 00AAH
Reserved
00ABH
Drive Rated Current
00ACH
Speed Feedback (U1-05)
00ADH
00AEH, 00AFH
Reserved
00B0H
Option Code Connected to CN5-A
00B1H
Reserved
00B2H
Option Code Connected to CN5-B
00B3H
Option Code Connected to CN5-C
00B4H
Reserved
00B5H
Output Speed After Soft Start
(U1-16)
00B6H
00B7H
Speed Reference
00B8H
00B9H to 00BEH
Reserved
00BFH
Lists the last to digits of operation error code oPE.
460
<3>
CRC Error
Data Length Error
Reserved
Parity Error
Overrun Error
Framing Error
Timeout
Reserved
r/min
<4>
0.01% units
Refer to U: Monitors on page 430
During Run
During Zero Speed
During Reverse Run
During Fault Reset Signal Input
During Speed Agree
Drive Ready
Alarm
Fault
During Operation Error (oPE)
During Momentary Power Loss
Motor 2 Selected
Reserved
ComRef status, NetRef status
ComCtrl status, NetCtrl status
Refer to Alarm Register Contents on page 467
Refer to U: Monitors on page 430
<2>
r/min units
<4>
0.01% units
Register contains ASCII code of the option card.
DI-A3 = 0x01
DO-A3 = 0x02
AO-A3 = 0x04
PG-B3 = 0x11
PG-X3 = 0x12
PG-F3 = 0x21
PG-E3 = 0x22
Communication Option: Register contains ASCII code of 1st and 3rd digit of the option card type number.
Example: Register value is 5353H for "SS" if a SI-S3 option card is installed.
r/min units
<4>
0.01% units
r/min units
<4>
0.01% units