YASKAWA L1000A Technical Manual page 73

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Model
CIMR-LU
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40112
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40150
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40180
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40216
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40260
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40304
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40370
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40450
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40605
+3
<1> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB.
<2> When using the wire of this gauge in accordance with IEC/EN 61800-5-1, install an ELCB, or use copper wire of 10 mm
Note: When connecting peripheral devices and options to the terminals –, +1, +3, B1, and B2, refer to the instruction manuals for each
device. For more information, contact Yaskawa or your nearest sales representative.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Recomm. Gauge
Terminal
AWG, kcmil
3/0
2/0
4/0
4/0
1 × 2P
1 × 2P
2/0 × 2P
2/0 × 2P
3/0 × 2P
3/0 × 2P
4/0 × 2P
4/0 × 2P
300 × 2P
300 × 2P
3/0 × 4P
3/0 × 4P
1/0
300 × 4P
300 × 4P
2/0
Wire Range
AWG, kcmil
1/0 to 4/0
1/0 to 4/0
1/0 to 4/0
3 to 4/0
4
4
1/0 to 4/0
1/0 to 4/0
1 to 4/0
1/0 to 4/0
4
4 to 2
2 to 300
2 to 300
1 to 250
3 to 3/0
4
4 to 300
1 to 600
1/0 to 600
3/0 to 600
1 to 325
2
2 to 350
2/0 to 600
2/0 to 600
3/0 to 600
1 to 325
2
2 to 350
3/0 to 600
3/0 to 600
4/0 to 600
3/0 to 600
1
1 to 350
4/0 to 300
4/0 to 300
3/0 to 300
3/0 to 300
1
1 to 3/0
3/0 to 300
3/0 to 300
1/0 to 300
1/0 to 300
1/0 to 300
4/0 to 300
4/0 to 300
1/0 to 300
1/0 to 300
2/0 to 300
3.7 Main Circuit Wiring
Screw
Tightening Torque
Nm (lb.in.)
Size
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
2
(AWG 8).
3
73

Hide quick links: