S1-05: DC Injection / Position Lock Time at Stop
Determines how long the drive should perform DC Injection at stop. In CLV and CLV/PM, S1-05 determines how long
Position Lock should be performed. A setting of 0.00 disables S1-05.
No.
S1-05
S1-06: Brake Release Delay Time
Determines the time that must pass after an Up/Down command is entered before the output terminal set for "Brake
control" (H2- = 50) is triggered.
Adjusting this delay time can help when there is not enough time to develop the appropriate amount of motor flux. Be
sure to also increase the time S1-04 when setting S1-06 to relatively long delay time.
No.
S1-06
S1-07: Brake Close Delay Time
Determines the time that must pass after zero speed is reached before the output terminal set for "Brake control"
(H2- = 50) is released.
No.
S1-07
S1-10: Run Command Delay Time
Sets the time the drive waits after receiving an Up/Down command before starting operation. The time set should give the
motor contactor enough time to close.
No.
S1-10
S1-11: Output Contactor Open Delay Time
Determines the time that must pass for an output terminal set for "Output contactor control" (H2- = 51) to be released
after the drive has stopped and drive output has been shut off.
No.
S1-11
S1-12: Motor Contactor Control During Auto-Tuning Selection
Note: Available in drive software PRG: 7016 or later.
Determines the state of the output contactor control command (H2- = 51) during Auto-Tuning. The contactor closes
as soon as the Enter key is pressed in the Auto-Tuning start menu.
No.
S1-12
<1> Setting 2 is available in drive software versions PRG: 7017 or later.
<2> The setting is 0 or 1 for software version PRG: 7016.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
DC Injection / Position Lock Time at Stop
Parameter Name
Brake Release Delay Time
Parameter Name
Brake Close Delay Time
Parameter Name
Run Command Delay Time
Parameter Name
Output Contactor Open Delay Time
Parameter Name
Motor Contactor Control during Auto-Tuning
5.11 S: Elevator Parameters
Setting Range
Default
0.00 to 10.00 s
0.60 s
Setting Range
Default
0.00 to 10.00 s
0.20 s
Setting Range
Default
0.00 to [S1-05]
0.10 s
Setting Range
Default
0.00 to 1.00 s
0.10 s
Setting Range
Default
0.00 to 1.00 s
0.10 s
Setting Range
Default
0 to 2
<1> <2>
5
0
259

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents