D.2 European Standards
Grounding
■
The drive is designed to be used in T-N (grounded neutral point) networks. If installing the drive in other types of
grounded systems, contact your Yaskawa representative for instructions.
CE Standards Compliance for DC Power Supply Input
■
To meet CE standards, the following fuses should be installed. For details, refer to
Figure D.2
Figure D.2 Example of DC Power Supply Input (two L1000A drives connected in series)
Note: 1. When connecting multiple drives together, make sure that each drive has its own fuse. If any one fuse blows, all fuses should be
replaced.
2. For an AC power supply, refer to
3. The recommended fuses and fuse holders are made by Fuji Electric.
Drive Model
CIMR-LU
Type
20008
CR2LS-50
20011
20014
CR2LS-75
20018
CR2LS-100
20025
CR2L-125
20033
CR2L-150
20047
CR2L-175
20060
CR2L-225
20075
CR2L-260
20085
CR2L-300
20115
CR2L-350
20145
CR2L-400
20180
CR2L-450
20215
CR2L-600
20283
20346
CS5F-800
20415
CS5F-1200
<1> DC is not available for UL standards.
<2> Manufacturer does not recommend a specific fuse holder for this fuse. Contact Yaskawa or your nearest sales representative on fuse
dimensions.
476
DC power supply
(converter)
+
_
YEC_common
Standard Connection Diagram on page
Table D.2 Fuses and Fuse Holders
DC Power Supply Input
<1>
Fuse
Fuse Holder
Rated
Short-circuit
Qty.
Type
Breaking
Current (kA)
200 V Class
2
CM-1A
2
CM-2A
100
2
200
Fuse
U/ T1
+1
V/ T2
_
W/ T3
Drive
Fuse
U/ T1
+1
V/ T2
_
W/ T3
Drive
58.
Drive Model
CIMR-LU
Qty.
40005
40006
1
40007
40009
40015
1
40018
40024
40031
40039
40045
40060
40075
<2>
40091
40112
40150
40180
40216
40260
40304
40370
40450
40605
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Figure
D.2.
M
M
DC Power Supply Input
Fuse
Rated
Short-circuit
Type
Qty.
Breaking
Current (kA)
400 V Class
CR6L-50
CR6L-75
CR6L-100
100
CR6L-150
CR6L-200
CR6L-250
CR6L-300
CR6L-350
CR6L-400
CS5F-600
200
CS5F-800
200
CS5F-1200
CS5F-1500
<1>
Fuse Holder
Type
Qty.
2
CMS-4
2
2
CMS-5
2
2
<2>
2
<2>