E2-03: Motor No-Load Current
Set the no-load current for the motor in amperes when operating at the rated frequency and the no-load voltage. The drive
sets E2-03 during the Auto-Tuning process (Rotational Auto-Tuning and Stationary Auto-Tuning 1, 2). The motor
no-load current listed in the motor test report can also be entered to E2-03 manually. Contact the motor manufacturer to
receive a copy of the motor test report.
No.
E2-03
Note: The display resolution depends on the rated output power of the drive. Models CIMR-LU20008 to 20033, 40005 to
40018, and 50003 to 50013 display values in 0.01 A units, while models CIMR-LU20047 to 20415, 40024 to
40605, and 50017 to 50200 display values in 0.1 A units.
E2-04: Number of Motor Poles
Set the number of motor poles to E2-04. If Auto-Tuning completes successfully, the value entered to T1-06 will
automatically be saved to E2-04.
No.
E2-04
E2-05: Motor Line-to-Line Resistance
Sets the line-to-line resistance of the motor stator winding. If Auto-Tuning completes successfully, this value is
automatically calculated. Enter this value as line-to-line and not for each motor phase.
If Auto-Tuning is not possible, contact the motor manufacturer to find out the line-to-line resistance or measure it
manually. When using the manufacturer motor test report, calculate E2-05 by one of the formulas below:
• E-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75°C (167°F).
• B-type insulation: Multiply 0.92 times the resistance value (Ω) listed on the test report at 75°C (167°F).
• F-type insulation: Multiply 0.87 times the resistance value (Ω) listed on the test report at 115°C (239°F).
No.
E2-05
E2-06: Motor Leakage Inductance
Sets the voltage drop due to motor leakage inductance as a percentage of motor rated voltage. This value is automatically
set during Auto-Tuning (Rotational Auto-Tuning, Stationary Auto-Tuning 1, 2).
No.
E2-06
E2-07: Motor Iron-Core Saturation Coefficient 1
Sets the motor iron saturation coefficient at 50% of the magnetic flux. If Rotational Auto-Tuning completes successfully,
then this value is automatically calculated and set to E2-07. This coefficient is used when operating with constant output.
No.
E2-07
E2-08: Motor Iron-Core Saturation Coefficient 2
Sets the motor iron saturation coefficient at 75% of the magnetic flux. If Rotational Auto-Tuning completes successfully,
then this value is automatically and set to E2-08. This coefficient is used when operating with constant output.
No.
E2-08
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Motor No-Load Current
Parameter Name
Number of Motor Poles
Parameter Name
Motor Line-to-Line Resistance
Parameter Name
Motor Leakage Inductance
Parameter Name
Motor Iron-Core Saturation Coefficient 1
Parameter Name
Motor Iron-Core Saturation Coefficient 2
5.5 E: Motor Parameters
Setting Range
Default
0 to [E2-01]
Determined by o2-04
Setting Range
Default
2 to 48
Setting Range
Default
0.000 to 65.000 Ω
Determined by o2-04
Setting Range
Default
0.0 to 40.0%
Determined by o2-04
Setting Range
Default
0.00 to 0.50
Setting Range
Default
E2-07 to 0.75
4
5
0.50
0.75
189