YASKAWA L1000A Technical Manual page 221

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

H4-02, H4-03: Multi-Function Analog Output Terminal FM Gain and Bias
H4-05, H4-06: Terminal AM Gain and Bias
Parameters H4-02 and H4-05 set the terminal FM and AM output signal level equal to 100% of the monitor (gain).
Parameters H4-03 and H4-06 set the bias added to the monitor output for terminals FM and AM. Both are set as a
percentage, where 100% equals 10 Vdc analog output. The output voltage of both terminals is limited to 10 Vdc.
Select an output signal range between 0 to +10 Vdc or -10 to +10 Vdc using parameters H4-07 and H4-08.
illustrates how gain and bias settings work.
No.
H4-02
H4-03
H4-05
H4-06
Using Gain and Bias to Adjust Output Signal Level
The output signal is adjustable while the drive is stopped.
Terminal FM
1.
View the value set to H4-02 (Terminal FM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-01 will be output from terminal FM.
2.
Adjust H4-02 viewing the monitor connected to the terminal FM.
3.
View the value set to H4-03 on the digital operator, terminal FM will output a voltage equal to 0% of the parameter
being set in H4-01.
4.
Adjust H4-03 viewing the output signal on the terminal FM.
Terminal AM
1.
View the value set to H4-05 (Terminal AM Monitor Gain) on the digital operator. A voltage equal to 100% of the
parameter being set in H4-04 will be output from terminal AM.
2.
Adjust H4-05 viewing the monitor connected to the terminal AM.
3.
View the value set to H4-06 on the digital operator, terminal AM will output a voltage equal to 0% of the parameter
being set in H4-04.
4.
Adjust H4-06 viewing the output signal on the terminal AM.
Example 1: Set H4-02 to 50% for an output signal of 5 V at terminal FM when the monitored value is at 100%.
Example 2: Set H4-02 to 150% for an output signal of 10 V at terminal FM when the monitored value is at 76.7%.
Figure 5.32
10 V
Output Voltage
5 V
0 V
0%
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Terminal FM Gain
Terminal FM Bias
Terminal AM Gain
Terminal AM Bias
H4-07, 08 = 0
Gain 150%
Bias 0%
Gain 100%
Bias 0%
Gain 50%
Bias 0%
100%
Monitor Value
Figure 5.32 Analog Output Gain and Bias Setting Example 1 and 2
5.7 H: Terminal Functions
Setting Range
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
-999.9 to 999.9%
H4-07, 08 = 1
15 V
Output Voltage
10 V
5 V
-100%
100%
Monitor Value
-5 V
-10 V
-15 V
Figure 5.32
Default
100.0%
0.0%
50.0%
0.0%
common_TMonly
Gain = 150%
5
Bias = 0%
Gain = 100%
Bias = 0%
Gain = 50%
Bias = 0%
221

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents