YASKAWA L1000A Technical Manual page 228

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

5.8 L: Protection Functions
L3-01: Stall Prevention Selection during Acceleration
Stall Prevention during acceleration (L3-01) prevents tripping with overcurrent (oC), motor overload (oL1), or drive
overload (oL2) faults common when accelerating with heavy loads.
L3-01 determines the type of Stall Prevention the drive uses during acceleration.
No.
L3-01
Setting 0: Disabled
No Stall Prevention is provided. If the acceleration time is too short, the drive may not be able to get the motor up to speed
fast enough, causing an overload fault.
Setting 1: Enabled
Enables Stall Prevention during acceleration.
If the output current rises above the Stall Prevention level set in L3-02, then the drive stops accelerating. Acceleration will
not resume until the output current falls 15% below the setting in L3-02.
The Stall Prevention level is automatically reduced in the constant power range.
Figure 5.37
Setting 2: Intelligent Stall Prevention
The drive disregards the selected acceleration time and attempts to accelerate in the minimum time. The acceleration rate
is adjusted so the current does not exceed the value set to parameter L3-02.
L3-02: Stall Prevention Level during Acceleration
Sets the output current level at which the Stall Prevention during acceleration is activated.
No.
L3-02
<1> The upper limit and default value are determined by the carrier frequency reduction (L8-38).
• Lower L3-02 if stalling occurs when using a motor that is relatively small compared to the drive.
• Also set parameter L3-03 when operating the motor in the constant power range.
228
Parameter Name
Stall Prevention Selection during Acceleration
Output current
Stall Prevention Level
During Acceleration
L3-02
L3-02
-15%
Output speed
Figure 5.37 Stall Prevention During Acceleration for Induction Motors
Parameter Name
Stall Prevention Level during Acceleration
Controls the output speed
to prevent the motor from stalling
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
0 to 2
common_TMonly
Time
Time
Setting Range
0 to 150%
<1>
Default
1
Default
<1>

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents