C5-08: Speed Control Loop Integral Limit
■
Sets the upper limit for Speed Control Loop output as a percentage of the rated torque.
No.
C5-08
C5-16: Speed Control Loop Delay Time during Position Lock
■
Adjusts the delay applied to the torque reference output from Speed Control Loop during Position Lock. Increase this
setting gradually in increments of 0.01 when vibration is a problem. This parameter rarely needs to be changed.
No.
C5-16
Speed Control Loop Delay Time during Position Lock
■
C5-17, C5-18: Motor Inertia, Load Inertia Ratio
C5-17 and C5-18 determine the ratio of the machine inertia and the inertia of the motor being used.
No.
C5-17
C5-18
C5-19, C5-20: Speed Control Loop P Gain Time, I Time during Position Lock
■
These parameters adjust the responsiveness of Speed Control Loop during Position Lock. Increase C5-19 and shorten
C5-20 if the motor rolls back immediately after the brake releases. Decrease C5-19 and lengthen C5-20 if vibrations
occur.
No.
C5-19
Speed Control Loop Proportional Gain Time during Position Lock
C5-20
Speed Control Loop Integral Time during Position Lock
C5-50: Set Vibrational Frequency Filter
■
Mechanical resonance may cause a humming sound or vibration while the motor is running. A vibrational frequency filter
can be used to suppress certain audible noise or vibration due to mechanical resonance.
Sets the mechanical vibration filter frequency in units of 1 Hz. Set C5-50 to 0 (Hz) to disable the filter. A setting of 0 will
disable this parameter.
Note: Test equipment may be required to determine the mechanical resonance frequency. Setting C5-50 to an improper frequency will
result in ineffective filtering of the effects of mechanical resonance.
No.
C5-50
<1>
<1> Available in drive software versions PRG: 7200 or later.
<2> The frequencies from 1 to 19 Hz cannot be set.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
P, I
0
Parameter Name
Speed Control Loop Integral Limit
Parameter Name
Parameter Name
Motor Inertia
Load Inertia Ratio
Parameter Name
Parameter Name
Set Vibrational Frequency Filter
P = C5-01
I = C5-02
P = C5-13
I = C5-14
Speed
C5-07
Setting Range
0 to 400%
Setting Range
0.000 to 0.500 s
Setting Range
0.0001 to 600.00 kgm
0.0 to 6000.0
Setting Range
0.00 to 300.00
0.000 to 10.000 s
Setting Range
0 Hz, 20 to 1000 Hz