5.
For the PG-B3 and PG-X3 Option, wire the motor PG encoder to the terminal block. Refer to
Figure 8.12
for wiring instructions.
Refer to Terminal Functions on page 360
Connecting PG-B3 Option
Parameter Settings and Connections for Different Encoder Types
• Connecting a Single-Pulse Encoder
When using a single-pulse encoder in V/f with PG control mode, connect the pulse output from the PG to the option and
set drive parameter F1-21 to 0.
• Connecting a Two-Pulse Encoder
When using a two-pulse encoder, connect the A and B pulse outputs on the PG to the option and set F1-21 to 1.
When using a two-pulse encoder in Closed Loop Vector control mode, connect pulse outputs A and B from the encoder
to the corresponding terminals on the option.
• Connecting a Two-Pulse Encoder with Z Marker Pulse
When using a two-pulse encoder with Z marker pulse, connect the A, B, and Z pulse outputs to the corresponding
terminals on the option.
Control Method
No. of Encoders
Single Pulse (A)
Two Pulse (AB Quadrature)
Two Pulse with Marker (ABZ)
Connection Diagram of PG-B3
Refer to
Table 8.3
for a detailed description of the option board terminal functions.
Refer to
Wire Gauges and Tightening Torques on page 361
<1> Ground the shield on the PG side and the drive side. If noise problems arise in the PG signal, remove the shield ground from one end of the
signal line or remove the shield ground connection on both ends.
Note: The PG-B3 Option reads a maximum input frequency from the PG encoder of 50 kHz. Be sure to select an PG encoder with an
output pulse frequency of maximum 50 kHz when operating at maximum speed.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
for a detailed description of the option terminal functions.
V/f with PG
1 (CN5-C)
F1-21 = 0
F1-21 = 1
F1-21 = 1
R/L1
U/T1
S/L2
V/T2
T/L3
W/T3
YASKAWA
Drive
CN5
FE
Ground wire
Twisted-pair shielded line
Main circuit terminal
Figure 8.8 PG-B3 Option and Encoder Connection Diagram
2 (CN5-B)
F1-37 = 0
F1-37 = 1
No setting required
F1-37 = 1
No setting required
for information on making cables.
TB1
3
PG B3
A+
4
Option
A
5
B+
6
B
Z+
Z
SD
NC
FE
E
TB2
1
IP
2
IG
AO
A pulse monitor signal
IG
BO
B pulse monitor signal
IG
ZO
Z pulse monitor signal
IG
Control circuit terminal
8.4 Option Card Installation
Figure 8.8
Closed Loop Vector
1 (CN5-C)
2 (CN5-B)
N/A
N/A
No setting required
No setting required
M
PG
B3
and
8
359