YASKAWA L1000A Technical Manual page 295

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Digital Operator Display
Cause
External operator is not properly connected to the drive.
Digital Operator Display
Cause
Overshoot is occurring.
Inappropriate parameter settings.
Digital Operator Display
Cause
Deceleration ramp is too short and regenerative energy
is flowing from the motor into the drive.
Fast acceleration ramp causes the motor to overshoot the
speed reference.
Surge voltage entering from the drive input power.
Ground fault in the output circuit causes the DC bus
capacitor to overcharge.
Drive input power voltage is too high.
The braking transistor is wired incorrectly.
Encoder cable is disconnected.
Encoder cable wiring is wrong.
Noise interference along the encoder wiring.
Drive fails to operate properly due to noise interference.
Motor hunting occurs.
Digital Operator Display
Cause
There is phase loss in the drive input power.
There is loose wiring in the drive input power terminals.
There is excessive fluctuation in the drive input power
voltage.
There is poor balance between voltage phases.
The main circuit capacitors are worn.
Digital Operator Display
Cause
During Rescue Operation, either the DC bus voltage
dropped below S4-12 × (S4-13 - 10%), or 100 ms after
triggering Rescue Operation, the DC bus voltage did not
reach S4-12 × S4-13 before the motor started.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
External Digital Operator Connection Fault
• The external operator has been disconnected from the drive.
Note:
oPr
An oPr fault will occur when all of the following conditions are true:
 Output is interrupted when the operator is disconnected (o2-06 = 1).
 The Up/Down command is assigned to the operator (b1-02 = 0 and LOCAL has been selected).
• Check the connection between the operator and the drive.
• Replace the cable if damaged.
• Turn off the drive input power and disconnect the operator. Then reconnect the operator and turn the drive input power back on.
Overspeed
oS
The motor speed feedback exceeded the F1-08 setting.
• Reduce the settings for C5-01 (Speed Control Proportional Gain 1) and increase C5-02 (Speed Control Integral Time 1).
• If using a closed loop vector mode, enable Inertia Compensation.
Check the setting for the overspeed detection level and the overspeed detection time (F1-08 and F1-09).
DC Bus Overvoltage
Voltage in the DC bus has exceeded the overvoltage detection level.
ov
• For 200 V class: approximately 410 V
• For 400 V class: approximately 820 V
• For 600 V class: approximately 1040 V
• Increase the deceleration ramp (C1-02, C1-04, C1-06, C1-08).
• Make sure the braking resistor rating/external braking transistor rating fits the application.
• If an external braking transistor is used, make sure it is connected properly and working as expected.
• Check if sudden drive acceleration triggers an overvoltage alarm.
• Increase the acceleration ramp (C1-01, C1-03, C1-05, C1-07).
• Increase the jerk setting in C2-02 (decrease if o1-03 > 3)
Install a DC link choke.
Note: Voltage surge can result from a thyristor convertor and phase advancing capacitor using the same input power supply.
• Check the motor wiring for ground faults.
• Correct grounding shorts and turn the power back on.
• Check the voltage.
• Lower drive input power voltage within the limits listed in the specifications.
• Check braking transistor wiring for errors.
• Properly rewire the braking resistor device.
Reconnect the cable.
Correct the wiring.
Separate the wiring from the source of the noise (often the output lines from the drive).
• Review the list of possible solutions provided for controlling noise.
• Review the section on handling noise interference and check the control circuit lines, main circuit lines, and ground wiring.
• Adjust the parameters that control hunting.
• Adjust the AFR time constant (n2-02 and n2-03).
Input Phase Loss
PF
Drive input power has an open phase or has a large imbalance of voltage between phases. Detected when L8-05 = 1, 2, 3
(enabled).
• Check for wiring errors in the main circuit drive input power.
• Correct the wiring.
• Ensure the terminals are tightened properly.
• Apply the tightening torque as specified in this manual.
• Check the voltage from the drive input power.
• Review the possible solutions for stabilizing the drive input power.
• Stabilize drive input power or disable phase loss detection.
• Check the maintenance time for the capacitors (U4-05).
• Replace the capacitor if U4-05 is greater than 90%. For instructions on replacing the capacitor, contact Yaskawa or a Yaskawa
representative.
Check for problems with the drive input power. If drive input power appears normal but the alarm continues to occur, replace
either the control board or the entire drive. For instructions on replacing the control board, contact Yaskawa or a Yaskawa
representative.
PF5
Rescue Operation Power Supply Deterioration Error
• Check the DC bus voltage setting for Rescue Operation (S4-12).
• Lower the speed reference set for Rescue Operation (S4-15).
• Check the backup power supply. It may need to be replaced with another UPS if it has become worn and can no longer provide
enough power.
6.3 Fault Detection
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Fault Name
Possible Solution
Refer to Wire Gauges and Tightening Torque on page
Fault Name
Possible Solution
69.
6
295

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents