5.11 S: Elevator Parameters
Run Command
(Forward [Up] / Reverse [Down])
H2-
= 53 (Not Zero
H2-
= 51
(Output Contactor
H1-
= 56
(Motor Contactor
Feedback)
H2-
= 50 (Brake
Control)
Operation
Speed
<1> Area S is the stopping distance (S5-12) from the point at which leveling operation is complete to when the car arrives at the designated
floor.
S5-10: Stopping Method Selection
■
Selects the stopping method.
No.
S5-10
Setting 0: Disable
Setting 1: Direct Landing
Setting 2: Leveling Distance Control
■
S5-11: Deceleration Distance
Sets the deceleration distance when Stop Distance Control is enabled.
No.
S5-11
<1> The setting range becomes 0.00 to 650.00 inches when the length units are set for inches (o1-12 = 1).
S5-12: Stop Distance
■
Sets the stopping distance when Stop Distance Control is enabled. Refer to
Distance Control on page 271
No.
S5-12
<1> The setting range becomes 0.00 to 393.00 inches when the length units are set for inches (o1-12 = 1).
S5-13: Direct Landing Minimum Speed Level
■
Sets the speed level for the start of Direct Landing. Direct Landing is disabled if the starting speed for Direct Landing is
less than the maximum output speed multiplied by this parameter (E1-04 × S5-13).
No.
S5-13
272
Speed)
Control)
Run Command Delay Time (S1-10)
Brake Release Delay Time
(S1-06)
Zero Speed
at Start
Figure 5.51 Operation Sequence Example for Leveling Distance Control
Parameter Name
Stopping Method Selection
Parameter Name
Deceleration Distance
for details.
Parameter Name
Stop Distance
Parameter Name
Direct Landing Minimum Speed Level
ON
OFF
ON
ON
ON
ON
Refer to Direct Landing on page 270
Direct Landing on page 270
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
OFF
OFF
Output Contactor Open
Delay Time (S1-11)
OFF
Brake Close
Delay Time
(S1-07)
Zero Speed
at Stop
S
<1>
Setting Range
0 to 2
Setting Range
0 to 32767 mm
<1>
and
Setting Range
0 to 10000 mm
<1>
Setting Range
0 to 100%
Time
Default
0
for details.
Default
0 mm
Leveling
Default
0 mm
Default
20%