Setting 1D: During regeneration
Terminal closes when the motor is driven in the regenerative mode. This function is only available in closed loop control
modes.
Setting 1E: Reset enabled
An output set for "Reset enabled" closes when the drive attempts to reset after a fault has occurred.
The fault reset function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to reset. If the drive cannot successfully reset within the number of attempts permitted
by L5-01, a fault will be triggered and the terminal set to 1E will open. Refer to
for details on automatic reset.
Setting 1F: Motor overload alarm (oL1)
The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection
level.
Setting 20: Drive overheat pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to
Overheat Alarm Level on page 235
Setting 2F: Maintenance period
Output closes when the IGBTs, cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components. Refer to
details.
Setting 30: During torque limit
Output closes when the motor is operating at the torque limit specified by the L7- parameters or an analog input. This
setting can only be used in OLV, CLV and CLV/PM control modes. Refer to
for details.
Setting 33: Within position lock bandwidth
Output closes when the motor rotor position is within the position lock bandwidth (S3-04) during Position Lock at start or
stop.
Setting 37: During frequency output
Output closes when the drive is outputting a frequency.
Status
Open
No frequency output from drive when stopped with baseblock, stopped with DC injection braking during initial excitation, or stopped with short circuit braking.
Closed
Drive is outputting frequency.
Figure 5.28
Up/Down command
During frequency
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
for details on drive overheat detection.
OFF
ON
Baseblock
OFF
command
Output
frequency
OFF
ON
During run
OFF
ON
Output
Figure 5.28 During Frequency Output Time Chart
L5: Automatic Fault Reset on page 231
Periodic Maintenance on page 323
L7-01 to L7-04: Torque Limits on page 234
Description
ON
5.7 H: Terminal Functions
L8-02:
common_
TMonly
for
5
215