YASKAWA L1000A Technical Manual page 271

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Run Command
(Forward [Up] / Reverse [Down])
H1-
= 5C
(Stop Distance Correction)
H2-
= 51
(Output Contactor
Control)
H1-
= 56
(Motor Contactor
Feedback)
H2-
= 50 (Brake Control)
Operation
Speed
<1> Area S1 is the deceleration distance (S5-11) from the start of deceleration to stop. Area S2 is the stopping distance (S5-12) from the point
at which the stopping distance compensation signal is entered to when the car arrives at the designated floor.
Leveling Distance Control
Leveling Distance Control (S5-10 = 2) uses the leveling speed reference for the remaining distance to arrive at the
designated floor. Leveling Distance Control is activated when the conditions listed in
Speed Priority Selection
Multi-step speed sequence
(d1-18 = 0, 3)
High speed reference has priority
(d1-18 = 1)
Multi-step speed sequence
(d1-18 = 2)
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
ON
Run Command Delay Time (S1-10)
Brake Release Delay Time
(S1-06)
Zero Speed
at Start
Figure 5.50 Direct Landing Operation Example
Table 5.16 Leveling Distance Control Operation
Multi-Function Input Terminal Settings
Leveling speed reference is selected
(H1- = 53).
Leveling speed reference is not selected
(H1- ≠ 53).
Rated speed reference is selected
(H1- = 50).
Rated speed reference is not selected
(H1- ≠ 50).
5.11 S: Elevator Parameters
OFF
OFF
Output Contactor Open
ON
Delay Time (S1-11)
ON
ON
Brake Close
Delay Time
(S1-07)
Zero Speed
S1
<1>
at Stop
S2
<1>
Table 5.16
are met.
Leveling Distance Control Start Conditions
The Up/Down command is not active or the speed reference is 0.
The Up/Down command is not active, or all input terminals set for
H1- = 50 to 53 are open.
Up/Down command is not active.
The Up/Down command is not active, or all input terminals set for
H1- = 50 to 53 are open.
Up/Down command is not active.
OFF
Time
5
271