7.4 Drive Cooling Fans and Circulation Fans
Installing the Cooling Fan
1.
Properly connect the fan power lines.
2.
Place the power supply connectors and cable back into the recess of the drive.
Figure 7.9
YEA_TMonly
Figure 7.9 Cooling Fan Power Supply Connectors: 20085, 20115, 40045, 40060, 50032, and 50041
3.
Install the replacement fan into the drive.
Figure 7.10
Figure 7.10 Installing the Cooling Fan: 20085, 20115, 40045, 40060, 50032, and 50041
4.
Tilt up the back end of the fan finger guard and slide the fan finger guard into the opening near the front of the
drive, then guide the fan finger guard into place.
Figure 7.11
Figure 7.11 Reattach the Fan Cover: 20085, 20115, 40045, 40060, 50032, and 50041
330
A – Back
YEA_TM
only
B – Front
Insert the fan at an angle so that
it tilts towards the front of the
drive. Next press down on the
back of the fan that still protrudes
from the drive so that the fan
snaps into place.
Insertion area
Front of drive
Cross-Section
Fan finger guard
Hook
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
A
B
Back of drive
YEA_
Back of drive
TMonly
Hook
Front of drive