C.4 MEMOBUS/Modbus Setup Parameters
■
H5-09: Communication Fault Detection Time
Sets the time the communications must be lost before the drive triggers a CE fault.
No.
H5-09
■
H5-10: Unit Selection for MEMOBUS/Modbus Register 0025H
Sets the unit for the output voltage monitor value in MEMOBUS/Modbus register 0025H.
No.
H5-10
Setting 0: 0.1 V units
Setting 1: 1 V units
H5-11: Communications Enter Function Selection
■
Selects whether an Enter command is necessary is needed to change parameter values via MEMOBUS/Modbus
communications.
Refer to Enter Command on page
No.
H5-11
Setting 0: Enter command necessary
Parameter changes become effective after an Enter command. An Enter command must only be sent after the last
parameter change, not for each single parameter.
Setting 1: Enter command not necessary
Parameter value changes become effective immediately without the need to send an Enter command.
450
Parameter Name
Communication Fault Detection Time
Parameter Name
Unit Selection for MEMOBUS/Modbus Register 0025H
Parameter Name
Communications Enter Function Selection
468.
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Setting Range
0.0 to 10.0 s
Setting Range
0 or 1
Setting Range
0 or 1
Default
2.0 s
Default
0
Default
0