YASKAWA L1000A Technical Manual page 485

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Model
CIMR-LU
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40260
<1>
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1
40304
<1>
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
40370
–, +1
<1> <2>
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
40450
–, +1
<1> <2>
+3
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
40605
–, +1
<1> <2>
+3
<1> Drive models CIMR-LU40045 to 40260 require the use of closed-loop crimp terminals for UL/cUL compliance. Use only the tools
recommended by the terminal manufacturer for crimping.
<2> When an EMC filter is installed, take additional measures to comply with IEC/EN 61800-5-1. Refer to
for details.
Note: Use crimp insulated terminals or insulated tubing for wiring these connections. Wires should have a continuous maximum
allowable temperature of 75°C (167°F) 600 V UL approved vinyl sheathed insulation. Ambient temperature should not exceed
40°C (104°F).
Table D.6 Wire Gauge and Torque Specifications (Three-Phase 600 V Class)
Model
CIMR-LU
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
50003
–, +1, +2
50004
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
50006
B1, B2
R/L1, S/L2, T/L3
U/T1, V/T2, W/T3
–, +1, +2
500010
B1, B2
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Recommended Gauge
Terminal
AWG, kcmil
500
500
4/0 × 2P
4/0 × 2P
300 × 2P
300 × 2P
3/0 × 4P
4/0 × 4P
1/0
300 × 4P
300 × 4P
2/0
Recomm. Gauge
Terminal
AWG, kcmil
14
14
10
14
14
10
10
14
Applicable Gauge
AWG, kcmil
2/0 to 600
2/0 to 600
3/0 to 600
1 to 325
2
2 to 350
3/0 to 600
3/0 to 600
4/0 to 600
3/0 to 600
1
1 to 350
4/0 to 300
4/0 to 300
3/0 to 300
3/0 to 300
1
1 to 3/0
3/0 to 300
3/0 to 300
1/0 to 300
1/0 to 300
1/0 to 300
4/0 to 300
4/0 to 300
1/0 to 300
1/0 to 300
2/0 to 300
Wire Range
AWG, kcmil
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
14 to 10
12 to 10
14 to 6
14 to 6
14 to 6
14 to 10
8
12 to 8
D.3 UL and CSA Standards
Screw
Tightening Torque
Size
Nm (lb.in.)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
18 to 23
M10
(159 to 204)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
32 to 40
M12
(283 to 354)
EMC Filter Installation on page 477
Screw
Tightening Torque
Nm (lb.in.)
Size
1.2 to 1.5
M4
(10.6 to 13.3)
1.2 to 1.5
M4
(10.6 to 13.3)
2.1 to 2.3
M4
(18.6 to 20.4)
2.0 to 2.5
M5
(17.7 to 22.1)
D
485

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents