YASKAWA L1000A Technical Manual page 241

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

L8-89: Current Monitoring Selection
Note: Available in drive software PRG: 7017 or later.
Enables or disables the Current Monitoring function. When this parameter is set to 1 (Enabled), the current monitoring
level (L8-99) is added to the conditions required to turn off the Motor Contactor Feedback command at a stop.
No.
L8-89
Setting 0: Disabled
Setting 1: Enabled
L8-99: Current Monitoring Level
Note: Available in drive software PRG: 7017 or later.
Sets the current monitoring level as a percentage of the drive's rated current. When the output current is equal to or below
the set level, the Motor Contactor Feedback command turns off if the current monitoring selection is enabled (L8-89 = 1).
This parameter is also used to activate the Motor Current Monitor (H2- = 5C).
No.
L8-99
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
Parameter Name
Current Monitoring Selection
Parameter Name
Current Monitoring Level
5.8 L: Protection Functions
Setting Range
Default
0, 1
Setting Range
Default
0.0 to 50.0%
10.0%
0
5
241

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents