YASKAWA L1000A Technical Manual page 47

200 v class: 1.5 to 110 kw (2 to 150 hp) 400 v class: 1.5 to 315 kw (2 to 500 hp) 600 v class: 1.5 to 160 kw (2 to 250 hp)
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Digital Operator Remote Installation
Digital Operator Dimensions
Installation Types and Required Materials
The digital operator mounts to an enclosure two different ways:
1.
External/face-mount installs the operator outside the enclosure panel
2.
Internal/flush-mount installs the operator inside the enclosure panel
Table 2.2 Digital Operator Installation Methods and Required Tools
Installation Method
Simplified installation with the digital
External/Face-Mount
operator is mounted on the outside of
the panel with two screws.
Encloses the digital operator in the
Internal/Flush-Mount
panel. The digital operator is flush
with the outside of the panel.
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project
construction. Failure to comply could result in damage to the drive. Place a temporary cover over the top of the drive during installation.
Remove the temporary cover before drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
External/Face-Mount
1.
Cut an opening in the enclosure panel for the digital operator as shown in
2.
Position the digital operator so the display faces outwards, and mount it to the enclosure panel as shown in
Figure
2.11.
Figure 2.10
YASKAWA ELECTRIC SIEP C710616 38F YASKAWA AC Drive - L1000A Technical Manual
12.2
(0.48) 1.6 (0.06)
YEA_TMonly
60 (2.36)
Figure 2.10 Digital Operator Dimensions
Description
Installation Support Sets
Installation Support Set A
(for mounting with screws through
holes in the panel)
Installation Support Set B
(for use with threaded studs that are
fixed to the panel)
Digital Operator
Figure 2.11 External/Face-Mount Installation
Installation holes (2-M3 screws, depth 5)
S / N : J007XE273710001
44 (1.73)
7.9 (0.31)
Minimum
50 (1.97)
Model
EZZ020642A
EZZ020642B
M3 × 6
Phillips recessed
pan head machine screw × 2
Enclosure panel
2.2 Mechanical Installation
Unit: mm (in.)
Required Tools
Phillips screwdriver (#1)
Phillips screwdriver (#1, #2)
Phillips screwdriver (#1)
Wrench 7 mm (0.28 in.)
Figure